4.5
Checks before starting & during operation
IMPORTANT
Liquid valves not fully opened! Liquid trap! Both valves should be fully
opened on the liquid line, in order to avoid trapping liquid.
Check that all valves are fully opened.
Set the essential parameters of the electronic controller in programming level 1 (refrigerant
type, compressor cut-out/cut-in settings, fan setpoint....) according to the required
application.
Emerson recommends to check the oil level in the compressor after starting and operation
conditions have stabilised, and to add oil if needed to ensure a sufficient oil level (halfway
up the sight glass).