Emerson Copeland EazyCool Series Quick Installation Manual

Emerson Copeland EazyCool Series Quick Installation Manual

Large outdoor condensing units

Advertisement

Quick Links

Date of last update: Oct-19
L
O
ARGE
UTDOOR
1. Install the condensing unit according to Application Guidelines C6.1.9 "Copeland EazyCool™ Large Outdoor
Condensing Units".
2. Prefill the unit with refrigerant and set all valves into the operating position.
3. Set up the unit controller (XMC25D) for the required application.
NOTE: The value of parameter D29 must be lower than the value C16-C17/2 (unit switching-off point) to avoid
the low-pressure alarm.
NOTE: The liquid line in OL(T)E units must be insulated to avoid air-moisture condensation and lack of
performance.
The XMC25D controller provides 2 programming levels:
Pr1 with direct access
Pr2 protected with a password: 321 (intended for experts)
Explanation of LED functionalities:
LED
Mode
On
Flashing
On
On
Flashing
On
Flashing
On
Flashing
On
Flashing
On
On
On
On
How to program the "Pr1" parameters:
Access pre-
program level
Access
or
program level
Access Pr1
Select item
or
Show value
Modify
or
Confirm and
store
EXIT
CC7.8.15/1019/E
C
ONDENSING
Function
Compressor 1 enabled
Anti-short cycle delay enabled
Condensing fans enabled
Bar display
Programming mode
PSI display
Programming mode
When browsing the service menu
In fast access menu
When browsing the alarm menu
A new alarm occurred
An alarm is occurring
Digital unloader solenoid On
In defrost
Evaporator fans - Liquid line solenoid valve On
Press simultaneously for about 3 seconds to access the pre-programming
level. The message rtC (real time clock) is displayed.
Press the Up or Down key until the message Par is displayed.
Press the SET button to enter the program level. First parameter C01 is
displayed.
Select the parameter or submenu using the arrows.
Press the SET button.
Use the arrows to modify the value.
Press the SET button: the value will blink for 3 seconds, then the display
will show the next parameter.
Press simultaneously to exit the programming mode, or wait
for 30 seconds (MTO) without pressing any key.
Ident number 3272062 – P/N 052-3306-00/Rev00
U
– Q
I
NITS
UICK
NSTALLATION
Ref: CC7.8.15/1019/E
Application Engineering Europe
G
UIDE
1/2

Advertisement

loading

Summary of Contents for Emerson Copeland EazyCool Series

  • Page 1 Date of last update: Oct-19 Ref: CC7.8.15/1019/E Application Engineering Europe – Q ARGE UTDOOR ONDENSING NITS UICK NSTALLATION UIDE 1. Install the condensing unit according to Application Guidelines C6.1.9 "Copeland EazyCool™ Large Outdoor Condensing Units". 2. Prefill the unit with refrigerant and set all valves into the operating position. 3.
  • Page 2 When entering the programming level for the first time the display will show the rtC (real time clock) label. ▪ Press to access parameters N01/02/03/04/05 to adjust time & date. For further details see the condensing unit application guidelines, chapter 2.11 "Parameters level 1 – Required settings". ▪...