Appendix 5: Alarm Menu - Emerson Copeland EazyCool ZXDI Series Application Manuallines

Indoor condensing units
Table of Contents

Advertisement

Appendix 5: Alarm menu

Code
Description
AI1 error (Probe 1/Suction pressure
E01
transducer failure alarm)
AI2 error (Probe 2/mid-coil
E02
temperature sensor failure alarm)
AI3 error (Probe 3/discharge line
E03
temperature sensor failure alarm)
AI4 error (Probe 4/PHE vapour inlet
E04
temperature sensor failure alarm)
AI5 error (Probe 5/PHE vapour
E05
outlet temperature sensor failure
alarm)
AI6 error (Probe 6/ambient
E06
temperature sensor failure alarm)
E07
AI7 error
E08
Battery error
E09
Current sensor 1 error
E10
Current sensor 2 error
E11
Voltage sensor 1 error
E12
Voltage sensor 2 error
E13
Voltage sensor 3 error
E14-E19 Reserved
C6.1.10/0118-0318/E
Cause
Action
Only in digital unit - compressor is
Probe failure or out of
activated according to C23, and
range
compressor on & off time is according
to D02 & D03
Probe failure or out of
The fan speed control is disabled
range
Probe failure or out of
The discharge temperature control is
range
disabled
Probe failure or out of
PHE superheat control is disabled
range
(ZXLE/ZXME unit)
Probe failure or out of
PHE superheat control is disabled
range
(ZXLE/ZXME unit)
Probe failure or out of
The functions related to probe 6
range
(ambient sensor) are disabled
Probe failure or out of
range
The functions related to current sensor
Probe out of range
are disabled
The functions related to current sensor
Probe out of range
are disabled
The functions related to current sensor
Probe out of range
are disabled
The functions related to current sensor
Probe out of range
are disabled
The functions related to current sensor
Probe out of range
are disabled
Reset
Automatically as soon as the probe restarts
working
Automatically as soon as the probe restarts
working
Automatically as soon as the probe restarts
working
Automatically as soon as the probe restarts
working
Automatically as soon as the probe restarts
working
Automatically as soon as the probe restarts
working
Automatically as soon as the probe restarts
working
Automatically as soon as the probe restarts
working
Automatically as soon as the probe restarts
working
Automatically: as soon as the probe restarts
working
Automatically as soon as the probe restarts
working
55