Alert Codes - Trane Hyperion AM8A0A24V21CA Series Field Reference Data

Convertible air handlers 2-5 ton
Table of Contents

Advertisement

Alert
Alert Group
Code
Assembly Text
18
Control failure
CNTRL FLT
19
Twinning fault
TWIN ERR
52
Indoor air sensor error
ICAS OPEN
52
Indoor air sensor error
ICAS SHORT
90
Communication busy fault
SYS COM CRC
SYS COMM
91
Communication inactive fault
91
Communication inactive fault
NO SYS CLK
92
Fuse failure
CHECK FUSE
104
Heater relay fault
104
Heater relay fault
ALL RLY OPEN
104
Heater relay fault
105
Heater interlock relay fault
BL INTLK OP
105
Heater interlock relay fault
BL INTLK CL
106
External shutdown fault
EXT SW OPEN
114
PM bad or missing fault
PM DATA ERR
114
ID motor error
ID MTR ERR
114
PM bad or missing fault
PM MISSING
114
PM bad or missing fault
PM UNIT ERR
114
PM bad or missing fault
PM MEM ERR
114
PM bad or missing fault
PM MISSING
114
ID motor error
MTR PWR HI
123
Demand configuration fault
EH CONFIG
EH ELMNT
152
Heater element fault
153
Thermal limit switch fault
EH CTCO TRIP
154
EH airflow limit fault
EH OFF/NO AF
154
EH airflow limit fault
EH LIM/NO AF
Indoor electronic expansion valve
155
EEV MTR ERR
motor fault
Indoor electronic expansion valve
155
EEV MTR ERR
motor fault
156
System low on charge fault
CONDESAT
157
Condensate fault
158
Coil freeze fault
ID COIL FRST
AFC COMM
159
Unit Bus fault
EHC COMM
EHC COMM
159
Unit Bus fault
HHC COMM
159
Unit Bus fault
EVC COMM
159
Unit Bus fault
CDA COMM
159
Unit Bus fault
160
Indoor EEV control configuration error
CONFIG FLT
161
Evaporator temperature sensor fault
ET SEN ERR
161
Gas temperature sensor fault
GT SEN ERR
163
Indoor EEV control fault
EEV CNTL FLT
164
Indoor EEV fault
EEV OPEN
164
Indoor electronic expansionvValve fault
166
Superheat is flooding fault
SYSTEM4 ERR
Indoor electronic expansion valve
167
OD DATA MISS
control is not controlling because
outdoor status is unknown
outdoor status is unknown
Indoor heat demand is not available to
168
hydronic heat control
Hydronic heat control configuration
169
HH CONFIG
fault
Hydronic heat control freeze condition
170
HH FRZ DET
detected
BLW COMM
171
Communication inactive fault
172
Display Assembly stuck key
KEY FAULT
Open coil freeze sensor (hydronic heat
173
HH FRZ OPEN
only)
Shorted coil freeze sensor (hydronic
173
heat only)
Notes:
1. * AFC STATUS LED will be solid ON during this fault•
2. COMM LED (amber) will flash the number of communicating devices connected
3. BM LED should be ON Solid when power is applied
4. STATUS LED will flash once per second in Idle mode.
Once a thermostat demand is received, it will flash 1 time/100 CFM requested
5. UNIT LED (blue) will flash once every four seconds when communications are norma
ALERT CODES FOR *AM8
Display
Notification
A/TCONT900
A/TZONE 950
ERR18
ERR 18.0
ERR19
ERR 19.0
Information
N/A
N/A
Information
N/A
N/A
Information
N/A
N/A
Information
ERR91
ERR 91.02
ERR
ERR91
ERR 91.03
N/A
N/A
EH RLY
ERR104
ERR 104.0
User Display
OPEN#
ERR104
ERR 104.02
EK RLY
ERR104
ERR 104.01
WELD#
ERR105
ERR 105.0
User Display
ERR105
ERR 105.01
User Display
ERR106
ERR 106.0
User Display
N/A
N/A
Information
ERR114
ERR 114.02
User Display
ERR114
ERR 114.03
N/A
N/A
Information
ERR114
ERR 114.05
ERR114
ERR 114.06
ERR114
ERR 114.07
User Display
ERR123
ERR 123.0
User Display
ERR152
ERR 152.0
User Display
OP#
ERR153
ERR 153.0
User Display
ERR154
ERR 154.0
ERR154
ERR 154.1
User Display
ERR155
ERR 155.0
User Display
ERR155
ERR 155.01
User Display
SYSTEM1
ERR156
ERR 156.0
User Display
ERR
ERR157
ERR 157.0
FLT
ERR158
ERR 158.0
User Display
ERR159
ERR 159.0
ERR
ERR159
ERR 159.01
User Display
ERR
ERR159
ERR 159.02
User Display
ERR
ERR159
ERR 159.03
User Display
ERR
ERR159
ERR 159.04
Information
ERR
ERR160
ERR 160.0
User Display
ERR161
ERR 161.0
User Display
ERR161
ERR 161.01
User Display
ERR163
ERR 163.0
User Display
EEV CLSE
ERR164
ERR 164.0
User Display
ERR
ERR164
ERR 164.01
User Display
ERR
ERR166
ERR 166.0
User Display
ERR167
ERR 167.0
User Display
HH FAULT
ERR168
ERR 168.0
User Display
ERR169
ERR 169.0
User Display
ERR170
ERR 170.0
User Display
ERR171
ERR 171.0
ERR
ERR172
ERR 172.0
User Display
ERR173
ERR 173.01
User Display
HH FRZ
ERR173
ERR 173.0
User Display
SHORT
AFC
EVC
EHC
HHC
Fault
Fault
Fault
Fault
Level
Code
Code
Code
Code
ON
Critical
8
6
6
3
Excessive communication errors
Critical
3
Loss of Heat/Cool demand message
Critical
3
Critical
1*
12
2
Critical
12
2
All heater relay stuck open error
Critical
12
3
Heater Relay Stuck Closed Error
12
8
Interlock Relay Stuck Open Error
12
8
Interlock Relay Stuck Closed Error
1
External shutdown input open error
2
PM data corrupt (Operation allowed)
Motor HP is < than PM value (Operation
2
PM missing with good local copy
Critical
2
Bad data in PM with good local copy
2
Bad data in PM with no local copy
Critical
2
PM missing with no local copy (Operation
Critical
2
Motor HP is > than PM value (Operation
2
12
6
12
4
12
5
Cycling thermal cut-out trip has occurred
Electric heat control locked out because of
Critical
12
7
Electric heat control is under restricted
12
7
operation because of insufficient airflow
EEV motor fault has been detected for 8
11
5
consecutive times and valve is locked out
EEV electric motor current indicates open
11
1
11
7
Critical
11
11
Condensate overflow condition detected
11
13
Indoor coil freeze condition detected
Critical
5
14
1
1
5
1
5
1
5
14
5
Display Assembly communication error
Configuration group index or evap
11
15
temperature sensor type are not
Indoor coil temperature sensor reading is
11
3
out of range, indicates open or short
Indoor coil temperature sensor reading is
11
4
out of range, indicates open or short
EEV electric motor drive or feedback or 12
11
2
EEV migrated to 'Close' position but
superheat is not at the desired set point,
11
6
valve is not responding to a change in
EEV migrated to 'Open' position but
superheat is not at the desired set point,
11
6
valve is not responding to a change in
11
10
11
16
Hydronic Heat is not controlling because
12
6
Indoor heat demand is not received
Hydronic heat capacity is unknown to
12
5
12
2
Hydronic heat coil freeze detected
Critical
4*
Blower Communication is not detected
Display Assembly has a stuck key
Hydronic coil freeze inlet temperature
12
4
sensor open condition detected
Hydronic coil freeze inlet temperature
12
3
sensor short condition detected
TAM8­22
Alert Description
Possible Cause
Internal Control Error
Control fault, replace AFC
More than one ID unit connected on the
Air handler twinning error
communicating bus is not allowed
Indoor air sensor is open
Sensor open, unplugged, wiring harness
Indoor air sensor is shorted
Sensor shorted, wiring harness
R & B to thermostat reversed polarity
Open / Shorted data line / CCM
communication error
Loss of Bit Master
Control fault, replace AFC
24V fuse open error
24VAC circuit short
Heater relay stuck open error
Heater relay failure
Heater relay failure
Heater relay failure, open element, open
non cycling limit switch
Blower interlock relay failure
Blower interlock relay failure
External float switch, other device open
Incorrect VS motor or PM installed
not allowed)
(Operation allowed)
(Operation allowed)
(Operation allowed)
not allowed)
Incorrect VS motor or PM installed
allowed)
KW jumper position on PARK
Electric heat configuration rrror
(replacement control only)
Heater element open
Low airflow, dirty coil/filter
Low airflow, dirty coil/filter
EHC locked out
insufficient airflow
Heater-Air handler mismatch
Faulty EEV motor / wiring harness
Faulty EEV motor / wiring harness
or short
System low on charge, liquid line
System 1 - High superheat
restriction, ET/GT sensor calibration
Condensate line clogged
Low / incorrect airflow, low refirgerant
charge, ET sensor calibration
Wire harness between AFC and
AFC communication error
distribution board
Wire harness between EHC and
Wi
h
EHC communication error
distribution board
Wire harness between HHC and
HHC communication error
distribution board
Wire harness between EVC and
EVC communication error
distribution board
Wire harness between Display Assembly
and distribution board
PM programming or internal
communication error
configured
Sensor open / shorted, unplugged, wiring
harness problem
Sensor open / shorted, unplugged, wiring
harness problem
EEV motor drive or motor feedback or 12v
V failure detected
Possible stuck valve, ET/GT sensor
position
Possible stuck valve, ET/GT sensor
position
Stuck valve, ET/GT sensor calibration,
System 4 - Low superheat
restricted distributor line that ET is
If Comm LED on OD unit is flashing the
OD status unknown to EVC
correct device count, replace AFC
If Unit LED on HHC is flashing once every
four seconds, replace HHC
Dip switch on HHC not set (replacement
hydronic heat control
Hydronic coil freeze inlet temperature
sensor reading is less than 38ºF
Faulty wiring harness, VS motor
Faulty Display Assembly
Sensor open, unplugged, wiring harness
Sensor short, wiring harness shorted
PM error
PM error
PM error
PM error
PM error
b t
EHC
d
failure
calibration
calibration
connected to
,
p
control only)
open