Alarm processing

6.2 Diagnostic alarms

Detailed information on DP slave diagnostics can be found in the SIMATIC Manual titled
ET 200S Distributed I/O System .
Alarm evaluation
Alarms sent by the I/O are evaluated in the PeripheralFaultTask. When the
PeripheralFaultTask is started, the Taskstartinfo is made available; you must evaluate this in
the user program. To do this, assign a program to the PeripheralFaultTask in the execution
system (see sample program Unit_E_FC_ctr).
The Taskstartinfo of PeripheralFaultTask is comparable to the local data of OB 82 in the
SIMATIC system.
Table 6-1
Meaning of the Taskstartinfo
Task
TSI
PeripheralFaultTask
DT
UDINT
DINT
DINT
DINT
DWORD TSI#details
6.2
Diagnostic alarms
Diagnostic alarms enable operational messages (hardware faults) of the ET 200S FC to be
detected in the SIMOTION device.
Definition of a diagnostic alarm
If the user program is to respond to an internal or external error, you can set the parameters
for a diagnostic alarm that will interrupt program execution in the SIMOTION device.
Events that trigger a diagnostic alarm
The criteria (events) for triggering diagnostic alarms in a SIMOTION system correspond to
those in a SIMATIC system.
34
Meaning
TSI#startTime
Start time of the task
TSI#interruptID
Identifies the triggering event:
● _SC_PROCESS_INTERRUPT
● _SC_DIAGNOSTIC_INTERRUPT
● _SC_STATION_DISCONNECTED
● _SC_STATION_RECONNECTED
TSI#logBaseAdrIn
Logical start address if a hardware interrupt (PRAL) or a diagnostic
interrupt (DAL) was caused by an input range on the module, oth‐
erwise _SC_INVALID_ADDRESS
TSI#logBaseAdrOut
Logical start address if a hardware interrupt (PRAL) or a diagnostic
interrupt (DAL) was caused by an output range on the module, oth‐
erwise _SC_INVALID_ADDRESS
TSI#logDiagAdr
Diagnostic address of a DP slave if the interrupt was caused by a
CPU stop or recovery of the associated DP slave, otherwise
_SC_INVALID_ADDRESS
Detail information (bit fields)
Supplement for the ET 200S frequency converter
Function Manual, 01/2015