Siemens SIMATIC ET 200S Function Manual page 12

Simotion supplement for the frequency converter
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Description
2.4 Inserting the ET 200S frequency converter into a SIMOTION project
Inserting the frequency converter
1. In SIMOTION SCOUT, open the "User Projects" dialog box with the "Project" > "Open"
menu command. In this dialog box, select your project and confirm with "OK".
2. Open HW Config.
3. In the "HW Config" window, open the hardware catalog with the "View" > "Catalog" menu
command.
4. In the hardware catalog, open the "PROFIBUS DP" folder and the "ET 200S" subfolder and
select, for example, the IM 151-1 Standard interface module (Article No.:
6ES7 151-1AA04-0AB0 or follow-on module).
5. Use a drag-and-drop operation to place the "IM 151-1 Standard" interface module on the
PROFIBUS subnet of your SIMOTION device.
The "Properties - PROFIBUS IM 151-1 Standard Interface" dialog box opens. In this dialog
box, select the address you set on the IM 151-1 (see
Manual) and confirm your selection with "OK".
The selected IM 151-1 Standard I/O device is inserted into the project.
6. The inserted I/O device still has to be equipped with the following modules: PM-D power
module and ET 200S FC frequency converter, consisting of ICU24 closed-loop control
module.
Open the "Motor starter" folder and the "PM" subfolder under "IM 151-1 Standard" in the
hardware catalog. Select the PM-D 24VDC power module.
You insert the frequency converter by selecting in the hardware catalog under
"IM151-1 Standard" (Article No.: 6ES7 151-1AA04-0AB0) in folder "Frequency converters"
the closed-loop control module ICU24 (Article No.: 6SL3244-0SA00-1AA0).
Note
You can disable or enable diagnostic alarms via parameter p8452 in the ET 200S frequency
converter.
7. Save and compile your project.
12
ET 200S Distributed I/O Device
Supplement for the ET 200S frequency converter
Function Manual, 01/2015