Configuring the AMPS-24
Interface Type
Select the interface type.
SLC: This must be selected when the AMPS-24 is used as the power supply for a CPU2-3030 or as
a remote power supply.
EIA-485: This must be selected when the AMPS-24 is used with an NCA-2.

Trouble Reporting

Select the trouble reporting option.
Five Point Monitoring: When the power supply is configured for Five Point Monitoring
(trouble reporting over the SLC), the panel will report a trouble message beginning at the base
SLC address. This selection must be made if the power supply is being used to power a CPU2-
3030 or as a remote power supply. Reporting at the base address ("Monitor General") includes
current limit, hardware failure, trouble bus active, and CPS communication trouble. Refer to
"SLC Addressing" on page 30
When the power supply is configured for Five Point Monitoring, the panel displays a specific
trouble message for AC Fail, Battery, Earth Fault, and Charger Fail addresses (See Table 3.1).
In CLIP mode, the labels for the "Base + x" addresses must be entered manually. In FlashScan
mode, device labeling is automatic.
36
Figure 3.6 PK-PPS: Interface Type
Figure 3.7 PK-PPS: Trouble Reporting
.
Programming the AMPS-24
AMPS-24 Manual — P/N 51907:J2 02/26/2014