Programming the AMPS-24
The worksheet's summary section displays all selections. When programming is complete, PK-PPS
displays the SLC address consumption that is the result of your selections.
Label
For greater ease of identification, you may create a label for each power supply. Labels may have a
maximum of 40 characters.
Outputs Current Settings
Choose the appropriate battery charger current for the system's battery capacity. Refer to
Section 4.2, "Calculating the Battery Requirements", on page 44 for more information on
determining your system's battery capacity.
There are three charger current options. Select
to 26 AH batteries. Select
when the batteries will be charged by an external charger (See "Setting the Charger" on page 26.).
NOTE: The charger current option "1A C
AMPS-24 Manual — P/N 51907:J2 02/26/2014
Figure 3.4 PK-PPS: Label
Figure 3.5 PK-PPS: Battery Charger/Outputs Current Setup
to charge 55 to 200 AH batteries. Select
5A C
HARGE
for 7 to 26AH,
1A C
HARGE
" is not approved for ULC applications.
HARGE
Configuring the AMPS-24
to charge 12
2A C
HARGE
D
C
ISABLE
HARGER
35