Honeywell Notifier AMPS-24/E Manual page 13

Table of Contents

Advertisement

LED Indicators
There are eighteen LEDs that indicate various conditions and troubles. The following table lists and
describes each.
Reference
LED Name
2
3
4
5
6
AMPS-K2
7
Board
8
9
10
11
12
13
1
2
CPS-24
3
Board
4
5
6
AMPS-24 Manual — P/N 51907:J2 02/26/2014
Color
STATUS
Green
RESET
Yellow
GEN TBL
Yellow
TBL BUS
Yellow
SLCRX
Green
SLCTX
Green
485TX
Green
485RX
Green
MAIN 24V
Green
MAIN 24V TBL
Yellow
AUX 24V TBL
Yellow
AUX 24V
Green
LOGIC POWER
Green
TROUBLE
Yellow
EARTH FAULT
Yellow
AC
Green
+24V AUX
Green
+5V AUX
Green
Table 1.3 LED Indicators
Description
+5V logic power and software indication
Normally slow blink (1 blink/sec)
Off in self-test failure or SLC address = 0 (bootloader)
Steady on memory Flashing and POR (+5V check)
RESET active.
Slow blink (1 blink/sec) if SLC address = 0 (bootloader)
Blinks once then pause in CPS communication failure
Fast blink (5 blinks/sec) in self-test failure or programming
Steady in any other trouble, POR and memory Flashing
Steady when external trouble bus signal received (trouble bus shorted)
SLC incoming data
SLC outgoing data
485 outgoing data
485 incoming data
+24V at Main output
Steady if in current-limit
Fast blink (5 blinks/sec) in hardware failure
Steady on memory Flashing, or RAM self-test failure
Medium blink (3 blinks/sec) on application code CRC self-test failure
Steady if in current-limit
Fast blink (5 blinks/sec) in hardware failure
• Steady on memory Flashing, PCB rev test failed
• Medium blink (3 blinks/sec) on application code CRC self-test failure
+24V at AUX output
+5V logic power
Coded trouble indicator: 1 blink = AC failure; 2 blinks - high battery; 3
blinks = low battery; 4 blinks = charger failure
Ground fault detected
AC is on
+24V Auxiliary power
+5V Auxiliary power
Introduction
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents