Honeywell Notifier ID3000 Series Installation & Commissioning Manual page 66

Fire control panels
Hide thumbs Also See for Notifier ID3000 Series:
Table of Contents

Advertisement

ID3000 Series Installation & Commissioning Manual
System Capacity:
Number of loops:
Number of zones:
Devices per loop:
External Connections:
Cable entry:
Terminals:
Electrical:
Classification:
Supply Rating
Mains supply to the panel is to be provided via an external
double-pole mains isolation unit. The supply rating is:
230V~(ac) ± 15%, 5A, 50Hz ±4%.
Fuse Rating (of terminal block):
T 5A 250V H Ceramic
Power Supply Unit (PSU) Specification
Kit PSU7A (PN:020-579).
For specification details, refer to 997-277-000-X (PSU7A
installation) and 997-267-000-X (DTP/Booster Installation)
Kit PSU3A (PN:020-648)
Maximum current consumption:
Output ratings:
Output voltage (boosted):
(PSU3A Unboosted output not used in ID3000)
Ripple voltage:
Max. output current quiescent:
Max. output current alarm:
EN54 Battery Wiring Test Impedance: 0.15 Ohm
EN54-4 PSU Loadings:
I
max(a)
Battery Charger Ratings:
Battery charger output:
Temperature compensation:
Battery fuse rating:
Final end battery voltage:
Charger ripple voltage:
Panel PSU Input Range:
A2 - 3
Up to 8 depending upon
configuration options.
Up to 255 per panel.
99 sensors + 99 modules or
99 sensors + combination of up to
99 modules/sounders within strict
limits. Use the loop & battery
calculator tool.
25 x 20mm knock-outs in top of
cabinet, 15 in rear, 4 in bottom.
All external connections made
through screw terminals, each of
which will accept cable sizes
between 0.5 mm
Installation Class I, (panel must be
earthed).
: 600mA @ 26Vdc; I
: 3.0A @ 26Vdc; I
max(b)
(measured at Baseboard Input)
and 2.5 mm
.
2
2
1.6A
26.0Vdc - 28.3Vdc
±300mV
600mA
3A
: 0mA
min
27.3V (nom) @ 20° C
-3mV/°C/cell
T 6.3A 250V H
(see
Appendix 1, Section 1.2)
21V
140mV rms
25.5Vdc - 28.5Vdc
997-274-000-6, Issue 6
September 2009