Honeywell Notifier ID3000 Series Installation & Commissioning Manual page 35

Fire control panels
Hide thumbs Also See for Notifier ID3000 Series:
Table of Contents

Advertisement

997-274-000-6, Issue 6
September 2009
ID3000 Series Installation & Commissioning Manual
5.5.3.1 Earthing the Front Cover
The earth lead (E) must be connected to the back box
prior to fitting the upper extension chassis (F) as follows:
1 Connect one end of the earth lead (E) to the blade
2 Rest the earth lead on the top surface of the U-shaped
3 Fit the upper zone extension and secure.
4 When offering the cover to the back box for fitting
5.5.3.2 Fitting the Front Cover
When the zone extension chassis have been fitted and
all wiring has been connected, fit the front cover as
follows:
1 Offer the cover (H) symmetrically and correctly
Note: To make sure the cover is correctly orientated, the
2 Use a 4mm hexagonal socket key to tighten each
3 To remove the cover, use the 4mm socket key to
CAUTION:
5.5.3.3 Label Inserts
Each extension chassis is provided with a vertical slot
behind the fascia to allow a label (M) to be inserted. Insert
the label as follows:
1 With the label correctly orientated, find the slot in the
2 Once the end has been inserted in the slot, straighten
30
terminal located on the right-hand side of the back
box (not shown).
channel (G).
(see below), first locate the free end of the earth lead
on the front cover's earth blade terminal.
orientated to the front of the back box.
top of the cover has a ledge (I) which locates on
the flange (J).
hexagonal socket-headed M6 screw (K).
unscrew the M6 screw (K).
Make sure the cover is supported when
releasing the last fastener.
top edge of the fascia and insert one corner to start.
the label and push in until all windows in the fascia
display the label text. A small amount of the label will
protrude above the fascia.