Troubleshooting; Logix Controller - Pentair AUTOTROL Performa 263 Installer Manual

Hide thumbs Also See for AUTOTROL Performa 263:
Table of Contents

Advertisement

Installer Manual Performa 263-268 / LOGIX 740-760 - Troubleshooting
10.

Troubleshooting

10.1. Logix controller

Err. code
Controller power has been connected
ERR 1
and the controller is not sure of the
operating status.
Controller power does not match 50 or
ERR 2
60 Hz.
Controller lost the position of
camshaft. Camshaft should be rotating
to find Home position.
Camshaft does not rotate.
ERR3
Camshaft rotates for more than 5
minutes to find Home position.
52 / 64
Cause
Reset and recovery
Reset controller.
See 6.4.3. Resetting the controller,
page 37.
Disconnect and reconnect the power.
If problem is not solved, obtain an
appropriate controller or AC
transformer.
Wait for 2 minutes: the controller
returns to Home position.
An hourglass icon flashes to indicate
that the motor is running.
Check:
Motor connections.
If motor wire harness is connected
to the motor.
If motor wire harness is connected
to the controller.
Optical sensor connection and
position.
If motor and camshaft gears are
engaged.
If everything is connected, try
replacing in this order:
Wire harness.
Motor.
Optical sensor.
Controller.
See 9.2. Cleaning and maintenance,
page 44.
Check:
Optical sensor connection and
position.
Camshaft connection.
Camshaft slots cleanness.
Ref. MKT-IM-011 / A - 15.06.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents