3.1.2.10 Write of Parameter for Analog Output Module

Write the value of a
single entry
Power Meter, IEC 60870-5-103, Manual
E50417-B1076-C375-A4, Release 11.2012
There is the possibility of changing parameters over the protocol IEC 60870-5-103.
This is carried out with the help of the generic data. The lists of the changeable param-
eter is contained in the mapping description for the respective device.
This function requests the device to accept new values of a single entry referenced by
its Generic Identification Number (GIN). The assignment of the GIN to the parameter
is contained in the mapping description for the respective device.
Generic data n
INF = 250
COT = 40
RII = x
CONT(NGD) = 0
COUNT(NGD) = previous
COUNT xor 1
Generic data (command
acknowledgement
INF = 250
COT = 40/41
RII = x
NO(NGD) = 0 with COT = 40
else NO(NGD) >= 0
GINs with GRC are transmitted
Figure 3-2 Write the value of a single enty
No.
Designation
1
AO1
Analog Output 1
2
AO2
Analog Output 2
1 actual value
GIN:
Generic Identification Number
KOD: Kind of Description
GDD: Generic Data Description
NGD: Number of Generic Data Set
SEN D
ASD U 10
(Generic data )
R ESPOND
ASD U 10
(Generic data )
Write the value
of a single entry
Type of
Description
Information
AO1
AO2
C ONFIRM
other transmission procedures
REQU EST
Polling for events
C lass 1
1
GIN
KOD
0x0101
1
0x0102
1
Data Mapping
GDD
NGD
4- INT
1
4- INT
1