4.2
Hardware Interface
Bus connection
Protocol
Max. line length
Insulation level
Bus termination
Power Meter, IEC 60870-5-103, Manual
E50417-B1076-C375-A4, Release 11.2012
9-pole D-SUB outlet
Pin
Signal
1
Shield
2
-
3
A
4
RTS
5
GND
EXT
6
+5 V
EXT
7
-
8
B
9
-
Table 4-1
Pin assignment of the bus connector (D-SUB outlet)
semi-duplex
1000 m / 3300 ft.
AC 500 V
Bus termination via bus plug with integrated terminating resistors.
A
B
Figure 4-1 Recommended external termination circuit with open-line fail-safe
Shield / Operational ground
-
RS485 connection pin A
Directions control
Data transmission level (ground towards +5 V
Supply voltage for terminating resistors (DC +5 V, max. 100 mA)
-
RS485 connection pin B
-
+5 V
EXT
390 Ohm
220 Ohm
390 Ohm
GND
EXT
Technical Data
Meaning
)
EXT
41