Endress+Hauser Levelflex M FMP45 Operating Instructions Manual

Endress+Hauser Levelflex M FMP45 Operating Instructions Manual

Guided level-radar
Hide thumbs Also See for Levelflex M FMP45:

Advertisement

Operating Instructions
Levelflex M FMP45
Guided Level-Radar
BA00279F/00/EN/15.11
71154965
Valid as of software version:
01.04.zz

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Levelflex M FMP45

  • Page 1 Operating Instructions Levelflex M FMP45 Guided Level-Radar BA00279F/00/EN/15.11 71154965 Valid as of software version: 01.04.zz...
  • Page 2 Levelflex M FMP45 4 to 20 mA HART Brief Operating Instructions KA189F/00/a2/03.07 Levelflex M - Brief operating instructions 52012501 Contrast: measured value dist./ meas value Group selection basic setup tank medium process empty full dist./ check range of start properties property cond.
  • Page 3: Table Of Contents

    Post-installation check ..... . 23 Contact addresses of Endress+Hauser ... 76 Wiring .
  • Page 4: Safety Instructions

    Safety instructions Levelflex M FMP45 4 to 20 mA HART Safety instructions Designated use The Levelflex M is a compact level transmitter for the continuous measurement of solids and liquids, measuring prinziple: Guided Level Radar / TDR: Time Domain Reflectometry.
  • Page 5: Notes On Safety Conventions And Icons

    Levelflex M FMP45 4 to 20 mA HART Safety instructions Notes on safety conventions and icons In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin.
  • Page 6: Identification

    Dat./Insp.: D01301-A Reference to additional safety-relevant documentation L00-FMP4xxxx-18-00-00-en-001 Information on the nameplate of the Levelflex M FMP45 2.1.2 Ordering structure This overview does not mark options which are mutually exclusive. Approval: A Non-hazardous area Non-hazardous area, WHG...
  • Page 7 Levelflex M FMP45 4 to 20 mA HART Identification Process temperature: A -200...+280 °C / -328...+5360 °F (XT); saturated steam max. +200 °C -200...+400 °C / -328...+7520 °F (HT) Special version, TSP-No. to be spec. Probe: A ..mm, rope 4mm, 316 C ..
  • Page 8 Identification Levelflex M FMP45 4 to 20 mA HART Type of probe: B Compact, centering disc d=45 mm, 316L, pipe diameter DN50/2" C Compact, centering disc d=75 mm, 316L, pipe diameter DN80/3" + DN100/4" Remote, cable 3m, top, center d=45 mm, centering disk d=45 mm, 316L, pipe diameter DN50/2"...
  • Page 9: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 10: Installation

    Installation Levelflex M FMP45 4 to 20 mA HART Installation Quick installation guide Mounting with threaded boss F12 or T12 housing Turn housing The housing can be turned 350° in order to simplify access to the display and the terminal compartment ½...
  • Page 11: Installation Conditions

    Levelflex M FMP45 4 to 20 mA HART Installation Installation conditions 3.3.1 Dimensions Housing dimensions 65 (2.56) 78 (3.07) max. 110 (4.33) ENDRESS+HAUSER F12 housing (Aluminium) 85 (3.35) mm (in) L00-F12xxxx-06-00-00-en-001 max. 100 (4.33) 94 (3.7) 65 (2.56) 78 (3.07)
  • Page 12 Installation Levelflex M FMP45 4 to 20 mA HART Process connection, type of probe F12 / T12 / F23 housing Variant “3” / “4” remote electronic top entry 4 x ø8,5 Variant “4”: remote electronic side entry ø21.3 ø76 ø76 ø81...
  • Page 13: Installation

    Levelflex M FMP45 4 to 20 mA HART Installation Installation 3.4.1 Mounting kit In addition to the tool needed for flange mounting, you will require the following tool: • For the mounting of threaded connection: 60 mm Open-end spanner for 1½".
  • Page 14 Installation Levelflex M FMP45 4 to 20 mA HART Coax probes The shortening is necessary if the distance to the container floor or outlet cone is less than 10 mm. Coax probes can be shortened max. 80 mm from the end. They have centering units inside which fix the rod centrally in the pipe.
  • Page 15 Levelflex M FMP45 4 to 20 mA HART Installation 3.4.4 Mounting rope probes in a partially full silo It is not always possible to empty a silo which is already in operation. Mounting in a partially filled silo is possible if the following conditions are met: •...
  • Page 16 Installation Levelflex M FMP45 4 to 20 mA HART 3.4.6 General instructions Normally use rod probes. Rope probes are used in liquids for measuring ranges > 4 m and with restricted ceiling clearance which does not allow the installation of rigid probes.
  • Page 17 Levelflex M FMP45 4 to 20 mA HART Installation Other installations • Select the mounting location such that the distance to internals (5) (e.g. limit switch, struts) is > 300 mm over the entire length of the probe, also during operation.
  • Page 18 Installation Levelflex M FMP45 4 to 20 mA HART Supporting probes against warping For WHG approval: For probe lengths ≥ 3 m a support is required (see figure). Rod probes Probe rod Sleeve bored tight to ensure electrical contact between the rod...
  • Page 19 Levelflex M FMP45 4 to 20 mA HART Installation Installing with heat insulation • If process temperatures are high (≥ 200 °C), FMP45 must be included in normal tank insulation to prevent the electronics heating up as a result of heat radiation or convection.
  • Page 20 In vacuum applications and in applications where extremely condensate fermation may occur, there is the danger that the vessel is completely flooded. For media groups with high DC values, this may result in a measuring value lower than the actual level. Please contact your local Endress+Hauser representative for remedial actions.
  • Page 21 Levelflex M FMP45 4 to 20 mA HART Installation 3.4.8 Notes on special installation situations Welding the probe into the vessel " Caution! Before welding the probe into the vessel, it must be grounded by a low-resistive connection. If this is not possible, the electronics as well as the HF module must be disconnected.
  • Page 22 Installation Levelflex M FMP45 4 to 20 mA HART 3.4.9 Installation for difficult to access process connections Installation with remote electronic • Wall and pipe bracket is contained in the scope of delivery and already mounted. • Follow installation instructions, Page 16 ff.
  • Page 23: Post-Installation Check

    Levelflex M FMP45 4 to 20 mA HART Installation 3.4.10 Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: •...
  • Page 24: Wiring

    Wiring Levelflex M FMP45 4 to 20 mA HART Wiring Quick wiring guide Wiring in F12/F23 housing " Before connection please note the following: The power supply must be identical to the data on the Caution! nameplate (1). ENDRESS+HAUSER Made in Germany...
  • Page 25 Levelflex M FMP45 4 to 20 mA HART Wiring Wiring in T12 housing " Before connection please note the following: The power supply must be identical to the data on the Caution! nameplate (1). ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg Switch off power supply before connecting up the device.
  • Page 26: Connecting The Measuring Unit

    Wiring Levelflex M FMP45 4 to 20 mA HART Connecting the measuring unit Terminal compartment Three housings are available: • Aluminium housing F12 with additionally sealed terminal compartment for: – standard, – Ex ia. • Aluminium housing T12 with separate terminal compartment for: –...
  • Page 27 Levelflex M FMP45 4 to 20 mA HART Wiring Cable entry Cable gland: M20x1.5 (only cable entry for Ex d) Cable entry: G½ or ½NPT Supply voltage HART, 2-wire The following values are the voltages across the terminals directly at the device:...
  • Page 28 Wiring Levelflex M FMP45 4 to 20 mA HART Overvoltage protection If the measuring device is used for the level measurement in flammable liquids which requires the use of an overvoltage protection according to EN/IEC 60079-14 or EN/IEC 60060-1 (10 kA, Puls 8/20 μs) it has to be ensured that...
  • Page 29: Recommended Connection

    Levelflex M FMP45 4 to 20 mA HART Wiring Recommended connection 4.3.1 Equipotential bonding Connect the Equipotential bonding to the external ground terminal (1) of the transmitter. F12/F23 housing T12 housing L00-FMP41Cxx-17-00-00-en-003 4.3.2 Wiring screened cable " Caution! In Ex applications, the device must only be grounded on the sensor side. Further safety instructions are given in the separate documentation for applications in explosion hazardous areas.
  • Page 30: Operation

    Operation Levelflex M FMP45 4 to 20 mA HART Operation Quick operation guide ENDRESS + HAUSER – >3 s Selection and configuration in Operation menu: 1.) Change from Measured Value Display to Group Selection by pressing 2.) Press to select the required Function Group (e.g..
  • Page 31 Levelflex M FMP45 4 to 20 mA HART Operation 5.1.1 General structure of the operating menu The operating menu is made up of two levels: • Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the device are split up roughly into different function groups.
  • Page 32: Display And Operating Elements

    Operation Levelflex M FMP45 4 to 20 mA HART Display and operating elements 5.2.1 Liquid crystal display (LCD) Four lines with 20 characters each. Display contrast adjustable through key combination. (liquid crystal display) Orde Orde Ser.- Ser.- r Cod No.: r Cod No.:...
  • Page 33 Levelflex M FMP45 4 to 20 mA HART Operation 5.2.3 Display symbols The following table describes the symbols that appear on the liquid crystal display: Sybmol Meaning ALARM_SYMBOL This alarm symbol appears when the device is in an alarm state. If the symbol flashes, this indicates a warning.
  • Page 34: Local Operation

    Operation Levelflex M FMP45 4 to 20 mA HART Local operation 5.3.1 Locking of the configuration mode The Levelflex can be protected in two ways against unauthorised changing of device data, numerical values or factory settings: Function "unlock parameter" (0A4): A value <>...
  • Page 35 There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the Endress+Hauser service organization. Please contact Endress+Hauser if you have any questions.
  • Page 36 Operation Levelflex M FMP45 4 to 20 mA HART 5.3.3 Factory settings (Reset) " Caution! A reset sets the device back to the factory settings. This can lead to an impairment of the measurement. Generally, you should perform a basic setup again following a reset.
  • Page 37: Display And Acknowledging Error Messages

    Levelflex M FMP45 4 to 20 mA HART Operation Display and acknowledging error messages Type of error Errors that occur during commissioning or measuring are displayed immediately on the local display. If two or more system or process errors occur, the error with the highest priority is the one shown on the display.
  • Page 38: Hart Communication

    The operating program FieldCare is an Endress+Hauser Plant Asset Management Tool based on FDT technology. You can use Field-Care to configure all your Endress+Hauser devices, as well as devices from other manufacturers that support the FDT standard. Hardware and software requirements you can find on the internet: www.endress.com ? select your country ? search: FieldCare ? FieldCare ? Technical Data.
  • Page 39 Levelflex M FMP45 4 to 20 mA HART Operation Signal analysis via envelope curve L00-FMP4xxxx-20-00-00-en-007 Tank linearization L00-fmp-Ixxx-20-00-00-en-041 Endress+Hauser...
  • Page 40: Commissioning

    Commissioning Levelflex M FMP45 4 to 20 mA HART Commissioning Function check Make sure that all final checks have been completed before you start up your measuring point: • Checklist "Post-installation check", → ä 23. • Checklist "Post-connection check", → ä 29.
  • Page 41: Basic Setup

    Levelflex M FMP45 4 to 20 mA HART Commissioning Basic Setup flange: reference point of measurement E = empty calibr. (= zero) LN = probe length setting in 005 setting in 033 F = full calibr. (= span) UB = upper blocking distance...
  • Page 42 Commissioning Levelflex M FMP45 4 to 20 mA HART " Caution! The basic setup is sufficient for successful commissioning in most applications. The Levelflex is initially adjusted at the factory to the probe length ordered, so that in most cases only the application parameters, that automatically adapt the device to the measuring conditions, need to be entered.
  • Page 43: Basic Setup With The Vu331

    Levelflex M FMP45 4 to 20 mA HART Commissioning Basic Setup with the VU331 Function "measured value" (000) ⇒ ENDRESS + HAUSER – This function displays the current measured value in the selected unit (see "customer unit" (042)) function). The number of digits after decimal point can be selected in the "no.of decimals"...
  • Page 44 Commissioning Levelflex M FMP45 4 to 20 mA HART bypass / pipe The "bypass / pipe" option is designed especially for the installation of probes in a bypass or a stilling well. If this option is selected, the upper blocking distance is preset to 100 mm.
  • Page 45 Levelflex M FMP45 4 to 20 mA HART Commissioning Function "process propert." (004) ⇒ ENDRESS + HAUSER – Use this function to adapt the device reaction to the filling speed in the tank. The setting impacts on an intelligent filter.
  • Page 46 Commissioning Levelflex M FMP45 4 to 20 mA HART Function "probe length" (031) ⇒ ENDRESS + HAUSER – Use this function to select whether the probe length was changed after factory calibration. Only then is it necessary to enter or correct the probe length.
  • Page 47 Levelflex M FMP45 4 to 20 mA HART Commissioning Function "determine length" (034) ⇒ ENDRESS + HAUSER – Use this function, the probe length can be determined automatically. Due to the mounting conditions, the automatically determined probe length may be larger than the actual probe (typically 20 to 30 mm longer).
  • Page 48 Commissioning Levelflex M FMP45 4 to 20 mA HART Function "full calibr." (006) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the minimum level to the maximum level (= span). 100% F = full calibration (= span) F max = E –...
  • Page 49 Levelflex M FMP45 4 to 20 mA HART Commissioning Function "check distance" (051) ⇒ ENDRESS + HAUSER – This function triggers the mapping of interference echoes. To do so, the measured distance must be compared with the actual distance to the product surface. The following options are available for...
  • Page 50 Commissioning Levelflex M FMP45 4 to 20 mA HART manual A mapping is also possible by manual entry of the range to be suppressed. This entry is made in the "range of mapping" (052) function. " Caution! The range of mapping must end 0.3 m (20") before the echo of the actual level. In case of empty vessel it is possible to make a map over the whole probe length.
  • Page 51 Levelflex M FMP45 4 to 20 mA HART Commissioning Function "dist./meas. value" (008) ⇒ ENDRESS + HAUSER – The distance measured from the reference point to the product surface and the meas. value calculated with the aid of the empty alignment are displayed again. Check whether the values correspond to the actual meas.
  • Page 52: Blocking Distance

    Commissioning Levelflex M FMP45 4 to 20 mA HART Blocking distance Function "upper block. dist" (059) ⇒ ENDRESS + HAUSER – For rod probes and for rope probes with lengths of up to 8 m, the upper blocking distance is preset to 0.2 m on delivery.
  • Page 53 Levelflex M FMP45 4 to 20 mA HART Commissioning Differing from this , the following measuring error is present in the vicinity of the probe end: DC = 2 DC = 80 DC = 80 A[mm] A[mm] 1 Rod and coax probe...
  • Page 54: Envelope Curve With Vu331

    Commissioning Levelflex M FMP45 4 to 20 mA HART Envelope curve with VU331 After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E)) function group) is recommended.). 6.6.1 Function "plot settings" (0E1) Here you can select which information is shown on the display: •...
  • Page 55: Function "Envelope Curve Display" (0E3)

    Levelflex M FMP45 4 to 20 mA HART Commissioning Function "envelope curve display" (0E3) You can obtain the following information from the envelope curve display in this function: quality of evaluated echo full calibr. evaluated echo empty calibr. is marked...
  • Page 56 Commissioning Levelflex M FMP45 4 to 20 mA HART 6.7.3 Mapping • Factory mapping Mapping (empty curve) is already available in the device when the device is delivered. • Customer mapping In a partially filled state, the distance up to 10 cm before the actual total level can be mapped (range of mapping = actual distance from total level - 10 cm), or values >...
  • Page 57 Levelflex M FMP45 4 to 20 mA HART Commissioning Move-Modus Then press , to switch to Move mode. Either is displayed. You now have the following options: • shifts the curve to the right. • shifts the curve to the left.
  • Page 58: Basic Setup With The Endress+Hauser Operating Program

    Commissioning Levelflex M FMP45 4 to 20 mA HART Basic setup with the Endress+Hauser operating program To carry out the basic setup with the operating program, proceed as follows: • Start the operating program and establish a connection. • Select the "basic setup" function group in the navigation window.
  • Page 59 Levelflex M FMP45 4 to 20 mA HART Commissioning Basic setup step 2/6: • Enter the application parameters (see chapter basic setup with "VU331"): – Tank properties – Medium properties – Process properties l00-fmp4xxxx-20-00-00-en-002 Basic setup step 3/6: • Enter the application parameters (see chapter basic setup with "VU331"): –...
  • Page 60 Commissioning Levelflex M FMP45 4 to 20 mA HART Basic setup step 4/6: • Enter the application parameters (see chapter basic setup with "VU331"): – Probe length – Probe – Probe length – Determine length l00-fmp4xxxx-20-00-00-en-004 Basic setup step 5/6: •...
  • Page 61 Levelflex M FMP45 4 to 20 mA HART Commissioning Basic setup step 6/6: • Interference echo suppression takes place in this step • The measured distance and the current measured value are always displayed in the header l00-fmp4xxxx-20-00-00-en-006.gif 6.8.1 Signal analysis via envelope curve After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope curve.
  • Page 62 Commissioning Levelflex M FMP45 4 to 20 mA HART Evaluating the measurement with the aid of the envelope curve Typical curve shapes: The following examples display typical curve shapes for a rope or rod probe in an empty tank. For all probe types, a negative probe end signal is shown.
  • Page 63 Levelflex M FMP45 4 to 20 mA HART Commissioning Evaluating the measurement: • The map must correspond to the course of the envelope curve (for rod probes up to approx. 5 cm and for rope probes up to approx. 25 cm before the end of the probe) when the tank is empty.
  • Page 64: Maintenance

    Repairs The Endress+Hauser repair concept assumes that the measuring devices have a modular design and that customers are able to undertake repairs themselves ("Spare Parts", Page 75). Please contact Endress+Hauser Service for further information on service and spare parts.
  • Page 65: Accessories

    Levelflex M FMP45 4 to 20 mA HART Accessories Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Levelflex M. Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code: 543199-0001).
  • Page 66: Remote Display And Operation Fhx40

    Accessories Levelflex M FMP45 4 to 20 mA HART Remote display and operation FHX40 Wall-mounting Pipe-mounting (without mounting bracket) (mounting bracket and plate supplied optionally, s. product structure) Separate housing FHX40 (IP 65) Micropilot M (4.8) Levelflex M Prosonic M...
  • Page 67: Centering Disks

    Levelflex M FMP45 4 to 20 mA HART Accessories Centering disks If the probes with rod version are used in stilling well or bypass, it must be ensured that the probe does not come into contact with the wall. The centering disk fixes the rod probe in the middle of the pipe.
  • Page 68: Commubox Fxa195 Hart

    For details refer to TI00404F/00/EN. Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field devices with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI00405C/07/EN. Note! For the device you need the "ToF Adapter FXA291" as an additional accessory.
  • Page 69: Special Process Connection

    Levelflex M FMP45 4 to 20 mA HART Accessories Special process connection 8.8.1 Fisher flange 249B/259B (MVTF N0123) 0,22" 1,125" L00-FMP45xxx-00-00-06-en-001 8.8.2 Fisher flange 249C (MVTF N0124) 0,188" 1,125" L00-FMP45xxx-00-00-06-en-002 8.8.3 Masoneillan flange (MVTF N0125) 0,25" 1,125" L00-FMP45xxx-00-00-06-en-003 Endress+Hauser...
  • Page 70: Trouble-Shooting

    Trouble-shooting Levelflex M FMP45 4 to 20 mA HART Trouble-shooting Trouble-shooting instructions Levelflex M -Trouble Shooting Check voltage and Not ok compare it with the Instrument does Connect the Instrument works? Ready specifications on the not respond correct voltage nameplate.
  • Page 71: System Error Messages

    Levelflex M FMP45 4 to 20 mA HART Trouble-shooting System error messages Code Description Possible cause Remedy A102 checksum error device has been powered off before data reset general reset & new calibr. could be stored; avoid emc problem; required emc problem;...
  • Page 72 Trouble-shooting Levelflex M FMP45 4 to 20 mA HART Code Description Possible cause Remedy A251 Feedthrough Lost contact in the process feedthrough Replace process feedtrough A261 HF cable defective HF cable defective or HF connector Check HF connector, replace cable...
  • Page 73: Application Errors

    Levelflex M FMP45 4 to 20 mA HART Trouble-shooting Application errors Error Output Possible cause Remedy A warning or alarm Depending on the configuration See table of 1. See table of error messages has occurred error messages (see Page 71) (see Page 71) →...
  • Page 74 Trouble-shooting Levelflex M FMP45 4 to 20 mA HART Error Output Possible cause Remedy Device displays a Incorrect probe length 1. Carry out automatic probe length level when the detection when the tank is tank is empty. empty. 20 mA/100% 2.
  • Page 75: Spare Parts

    Levelflex M FMP45 4 to 20 mA HART Trouble-shooting Spare Parts An overview of the spare parts for your device is available in the internet at www.endress.com. To obtain information on the spare parts, proceed as follows: Go to "www.endress.com" and select your country.
  • Page 76: Return

    Levelflex M FMP45 4 to 20 mA HART Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present.
  • Page 77: Technical Data

    Levelflex M FMP45 4 to 20 mA HART Technical data Technical data 10.1 Additional technical data 10.1.1 Input Measured variable The measured variable is the distance between a reference point (see Fig., see Page 12) and the product surface. Subject to the input empty distance "E", the level is calculated. Alternatively, the level can be converted by means of linearisation (32 points) into other variables (volume, mass).
  • Page 78 Technical data Levelflex M FMP45 4 to 20 mA HART Influence of ambiente The measurements are carried out in accordance with EN 61298-3: temperature • digital output: – average T : 0.6 mm/10 K, max. ±3.5 mm over the entire temperature range -40 °C to +80 °C.
  • Page 79 Levelflex M FMP45 4 to 20 mA HART Technical data Installing FMP45 with Application Gasphase Compensation For level measurement in steam applicatioins at high presures and temperatures. (Coax only) At high pressures and temperatures, the speed at which microwave signals are propagated in steam (polare media) is reduced above the liquid being measured.
  • Page 80 Technical data Levelflex M FMP45 4 to 20 mA HART 10.1.4 Operating conditions: Environment Ambient temperature range Ambient temperature for the transmitter: -40 °C to +80 °C. The functionality of the LCD display may be limited for temperatures Ta < -20 °C and Ta > +60 °C. A weather protection cover should be used for outdoor operation if the device is exposed to direct sunlight.
  • Page 81 Levelflex M FMP45 4 to 20 mA HART Technical data Storage temperature -40 °C to +80 °C. Climate class DIN EN 60068-2-38 (test Z/AD) Vibration resistance DIN EN 60068-2-64 / IEC 68-2-64: 20 to 2000 Hz, 1 (m/s Cleaning the probe Depending on the application, contamination or build-up can accumulate on the probe.
  • Page 82 Technical data Levelflex M FMP45 4 to 20 mA HART 10.1.5 Operating conditions: Process Process temperature range The maximum permitted temperature at the process connection (see Figure for measuring point) is determined by the process connection ordered: FMP45: process pressure depending on the process temperature...
  • Page 83 Levelflex M FMP45 4 to 20 mA HART Technical data 10.1.6 Mechanical construction Material See TI00386F/00/EN, chapter "Material (not in contact with process)" and "Material (in contact with process)". Tolerance of probe length Rod probes Rope probes over (m / ft) 1 (3.2)
  • Page 84 The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Manufacturer declaration Permitted pressures, temperatures and load cycles as per EN 13445 and AD- data sheet S2 (for FMP45).
  • Page 85 Levelflex M FMP45 4 to 20 mA HART Technical data 1) Housing F12/F23/T12-OVP: In combination with electronics B, D or F supply intrinsically safe. * in preparation Overspill protection WHG. See "Ordering structure", Page 6 (ZE00256F/00/DE). SIL 2, for 4 to 20 mA output (see SD00174F/00/EN "Functional safety manual").
  • Page 86: Appendix

    Appendix Levelflex M FMP45 4 to 20 mA HART Appendix 11.1 Operating menu HART (Display modul) basic setup tank properties medium cond. process proper. empty calibr. end of probe 030 determine length see Function group “leghth adjustment 03” enter value...
  • Page 87 Levelflex M FMP45 4 to 20 mA HART Appendix full calibr. dist./meas.value check distance range of mapping start mapping dist./meas.value enter value distance = ok input of D and L dist. too small mapping range are displayed D and L...
  • Page 88: Patents

    Appendix Levelflex M FMP45 4 to 20 mA HART 11.2 Patents This product may be protected by at least one of the following patents. Further patents are pending. • US 5,661,251 i EP 0 780 664 • US 5,827,985 i EP 0 780 664 •...
  • Page 89: Index

    Levelflex M FMP45 4 to 20 mA HART Index Index Accessories ........65 Maintenance .
  • Page 90 Levelflex M FMP45 4 to 20 mA HART Index Endress+Hauser...
  • Page 91 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 92 www.endress.com/worldwide BA00279F/00/EN/15.11 71154965 71154965 CCS/FM+SGML 6.0/ProMoDo...