Brief Operating Instructions
Levelflex M FMP45
Guided Level-Radar
These are Brief Operating Instructions.
For more detailed information, please refer to the Operating Instructions and the
additional documentation on the CD-ROM provided.
These Brief Operating Instructions are not intended to replace the Operating
Instructions provided in the scope of supply.
The complete device documentation consists of:
• these Brief Operating Instructions
• Approvals and safety certificates
• a CD-ROM with:
– the Operating Instructions
– Technical Information
KA01045F/00/EN/13.10
71120328

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Levelflex M FMP45

  • Page 1 Brief Operating Instructions Levelflex M FMP45 Guided Level-Radar These are Brief Operating Instructions. For more detailed information, please refer to the Operating Instructions and the additional documentation on the CD-ROM provided. These Brief Operating Instructions are not intended to replace the Operating Instructions provided in the scope of supply.
  • Page 2: Table Of Contents

    Table of contents Levelflex M FMP45 PROFIBUS PA Table of contents 1 Safety instructions ..........3 1.1 Designated use .
  • Page 3: Safety Instructions

    Levelflex M FMP45 PROFIBUS PA Safety instructions Safety instructions Designated use The Levelflex M is a compact level transmitter for the continuouse measurement of solids and liquids, measuring prinziple: Guided Level Radar / TDR: Time Domain Reflectometry. Installation, commissioning and operation •...
  • Page 4: Safety Icons

    Safety instructions Levelflex M FMP45 PROFIBUS PA Safety icons Symbol Meaning Warning! A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury, a safety hazard or destruction of the instrument. " Caution! Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or incorrect functioning of the instrument.
  • Page 5: Mounting

    Levelflex M FMP45 PROFIBUS PA Mounting Mounting Quick installation guide Mounting with threaded boss F12/F23 or T12 housing 1½" AF 60 Caution! Use only the threaded boss L00-FMP4xxxx-17-00-00-en-072 Incoming acceptance, transport, storage 2.2.1 Incoming acceptance Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
  • Page 6: Installation

    Mounting Levelflex M FMP45 PROFIBUS PA Installation 2.3.1 Mounting kit In addition to the tool needed for flange mounting, you will require the following tool: • For the mounting of threaded connection: 60 mm Open-end spanner for 1½". • 4 mm Allen wrench for turning the housing.
  • Page 7 Levelflex M FMP45 PROFIBUS PA Mounting 2.3.3 Mounting rope probes " Caution! If there is a risk of electrostatic discharge from the product, then both process connection and rope must be earthed before the probe is lowered into the silo.
  • Page 8 Mounting Levelflex M FMP45 PROFIBUS PA 2.3.5 Mounting the probe rod See KA00228F/00/B8. 2.3.6 General instructions Normally use rod probes. Rope probes are used in liquids for measuring ranges > 4 m and with restricted ceiling clearance which does not allow the installation of rigid probes.
  • Page 9 Levelflex M FMP45 PROFIBUS PA Mounting Minimum distance B of rod and rope probes to the container wall: The wall clearance can be chosen as desired as long as the probe does not touch the tank wall. Note! There should no bridges to the wall created by soiling or highly viscous media.
  • Page 10 Mounting Levelflex M FMP45 PROFIBUS PA Supporting probes against warping • For WHG approval: For probe lengths ≥ 3 m a support is required (see figure). Probe rod Sleeve bored tight to ensure electrical contact between the rod and sleeve! Short metal pipe e.g.
  • Page 11 Levelflex M FMP45 PROFIBUS PA Mounting 2.3.7 Special instructions When installing in stirring tanks, observe lateral load of probes. Possibly check whether a non-contact radar would not be better suited, above all if the stirrer generates large mechanical loads on the probe.
  • Page 12 Mounting Levelflex M FMP45 PROFIBUS PA " Caution! In vacuum applications and in applications where extremely condensate fermation may occur, there is the danger that the vessel is completely flooded. For media groups with high DC values, this may result in a measuring value lower than the actual level. Please contact your local Endress+Hauser representative for remedial actions.
  • Page 13 Levelflex M FMP45 PROFIBUS PA Mounting Installation in plastic containers Please note that the "guided level radar" measuring principle requires a metallic surface at the process connection! When installing rod or robe probes in plastic silos, whose silo cover is made of plastic or silos with wood cover, the probes must either be mounted in a ≥...
  • Page 14: Post-Installation Check

    Mounting Levelflex M FMP45 PROFIBUS PA 2.3.9 Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: •...
  • Page 15: Wiring

    Levelflex M FMP45 PROFIBUS PA Wiring Wiring Warning! When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings. " Caution! Before connection please note the following: •...
  • Page 16: Wiring In T12 Housing

    Wiring Levelflex M FMP45 PROFIBUS PA Wiring in T12 housing Unscrew housing cover (1). Insert cable (2) through gland (3). Connect cable screen to the grounding terminal (4) within the terminal compartment. Make connection (see terminal assignment). Tighten cable gland (6).
  • Page 17: Terminal Assignment

    Levelflex M FMP45 PROFIBUS PA Wiring Terminal assignment plant ground PA- PA+ L00-FMP4xxxx-04-00-00-en-007 Cable specification PROFIBUS Twisted, screened pairs must be used. The following cable types can be used, for example: • Siemens 6XV1 830-5BH10 • Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL • Belden 3076F...
  • Page 18: Connection With M12 Plug

    Wiring Levelflex M FMP45 PROFIBUS PA Supply voltage The following values are the voltages across the terminals directly at the instrument: Type Terminal voltage Standard 9 V to 32 V Supply voltage 9 V to 32 V Lift-off voltage There may be additional restrictions for devices with an explosion protection certificate. Refer to the notes in the appropriate Safety Instructions (XA).
  • Page 19: Screening/Potential Matching

    Levelflex M FMP45 PROFIBUS PA Wiring Screening/potential matching • You achieve optimum screening against disturbances if the screening is connected on both sides (in the cabinet and on the device). If you have to reckon with potential equalisation currents in the plant, only earth screening on one side, preferably at the transmitter.
  • Page 20: Operation

    Operation Levelflex M FMP45 PROFIBUS PA Operation General structure of the operating menu The operating menu is made up of two levels: • Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the instrument are split up roughly into different function groups.
  • Page 21: Display And Operating Elements

    Levelflex M FMP45 PROFIBUS PA Operation The third digit numbers the individual functions within the function group: → • basic setup • tank properties • medium properties • process cond. Here after the position is always given in brackets (e.g. "tank properties" (002)) after the described function.
  • Page 22 Operation Levelflex M FMP45 PROFIBUS PA 4.2.2 Display Headline Position indicator ENDRESS + HAUSER Symbol Main value Bargraph Unit – Selection list Function groups -> Functions HOME F000 F001 F002 F003 F004 ... FG00 FG01 FG02 Help text FG03 FG04...
  • Page 23: Display Symbols

    Levelflex M FMP45 PROFIBUS PA Operation 4.2.3 Display symbols The following table describes the symbols that appear on the liquid crystal display: Symbol Meaning ALARM_SYMBOL This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a warning.
  • Page 24: Device Address

    Operation Levelflex M FMP45 PROFIBUS PA Device address 4.3.1 Software addressing Software addressing comes into operation, when DIP-switch 8 is in the position "ON". BA034S/04/EN describes, how to set the address in this case. 4.3.2 Hardware addressing T II T II...
  • Page 25: Commissioning

    Levelflex M FMP45 PROFIBUS PA Commissioning Commissioning Function check Make sure that all final checks have been completed before you start up your measuring point: • Checklist "Post-installation check", → ä 14. • Checklist "Post-connection check", → ä 19. Switching on the measuring device...
  • Page 26: Overview Basic Setup

    Commissioning Levelflex M FMP45 PROFIBUS PA Overview Basic Setup flange: reference point of measurement E = empty calibr. (= zero) LN = probe length setting in 005 setting in 033 F = full calibr. (= span) UB = upper blocking distance...
  • Page 27 Levelflex M FMP45 PROFIBUS PA Commissioning " Caution! The basic setup is sufficient for successful commissioning in most applications. The Levelflex is initially adjusted at the factory to the probe length ordered, so that in most cases only the application parameters, that automatically adapt the device to the measuring conditions, need to be entered.
  • Page 28: Basic Setup With The Device Display

    Commissioning Levelflex M FMP45 PROFIBUS PA Basic Setup with the device display 5.4.1 Function "measured value" (000) ⇒ ENDRESS + HAUSER – This function displays the current measured value in the selected unit (see "customer unit" (042) function). The number of digits after decimal point can be selected in the "no.of decimals"...
  • Page 29 Levelflex M FMP45 PROFIBUS PA Commissioning Note! If "aluminium tank" is selected, the device calibrates of its own accord when first filled, depending on the medium's properties. Slope errors can, therefore, occur when beginning the first filling procedure. plastic tank Select the "plastic tank"...
  • Page 30 Commissioning Levelflex M FMP45 PROFIBUS PA ε Media group DC ( Typical liquids Typ. measuring range 1.4 to 1.6 – Condensed gases, e.g. N , CO 4m (157"), when installed in metallic pipes – Liquefied gas, e.g. Propane – Solvent 1.6 to 1.9...
  • Page 31 Levelflex M FMP45 PROFIBUS PA Commissioning 5.4.5 Function "process propert." (004) ⇒ ENDRESS + HAUSER – Use this function to adapt the device reaction to the filling speed in the tank. The setting impacts on an intelligent filter. Selection: • standard •...
  • Page 32 Commissioning Levelflex M FMP45 PROFIBUS PA 5.4.7 Function "probe length" (031) ⇒ ENDRESS + HAUSER – Use this function to select whether the probe length was changed after factory calibration. Only then is it necessary to enter or correct the probe length.
  • Page 33 Levelflex M FMP45 PROFIBUS PA Commissioning 5.4.10 Function "determine length" (034) ⇒ ENDRESS + HAUSER – Use this function, the probe length can be determined automatically. Due to the mounting conditions, the automatically determined probe length may be larger than the actual probe (typically 20 to 30 mm longer).
  • Page 34 Commissioning Levelflex M FMP45 PROFIBUS PA 5.4.12 Function "full calibr." (006) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the minimum level to the maximum level (= span). 100% F = full calibration (= span) F max = E –...
  • Page 35 Levelflex M FMP45 PROFIBUS PA Commissioning 5.4.14 Function "check distance" (051) ⇒ ENDRESS + HAUSER – This function triggers the mapping of interference echoes. To do so, the measured distance must be compared with the actual distance to the product surface. The following options are available...
  • Page 36 Commissioning Levelflex M FMP45 PROFIBUS PA distance = ok Use this function at part-covered probe. Choosing function "manual" or "probe free" at free probe. • mapping is carried out up to the currently measured echo • The range to be suppressed is suggested in the "range of mapping" (052) function Anyway, it is wise to carry out a mapping even in this case.
  • Page 37 Levelflex M FMP45 PROFIBUS PA Commissioning 5.4.16 Function "start mapping" (053) ⇒ ENDRESS + HAUSER – This function is used to start the interference echo mapping up to the distance given in "range of mapping" (052). Selection: • off: no mapping is carried out •...
  • Page 38: Blocking Distance

    Commissioning Levelflex M FMP45 PROFIBUS PA Blocking distance Function "upper block. dist" (059) ⇒ ENDRESS + HAUSER – For rod probes and for rope probes with lengths of up to 8 m, the upper blocking distance is preset to 0.2 m on delivery. For rope probes with lengths of more than 8 m, the upper blocking distance is preset to 2.5 % of the probe length.
  • Page 39 Levelflex M FMP45 PROFIBUS PA Commissioning Maximum measured error Typical statements for reference conditions: DIN EN 61298-2, percentage of the span. Output: digital analog sum of non-linearity, measurig range: ± 0.06 % non-repeatabilityand hysteresis – up to 10 m: ±3 mm –...
  • Page 40: Envelope Curve With Device Display

    Commissioning Levelflex M FMP45 PROFIBUS PA L00-FMP4xxxx-14-00-06-xx-001 Envelope curve with device display After the basic setup, an evaluation of the measurement with the aid of the envelope curve "envelope curve" (0E) function group) is recommended. 5.6.1 Function "plot settings" (0E1) Here you can select which information is shown on the display: •...
  • Page 41 Levelflex M FMP45 PROFIBUS PA Commissioning 5.6.2 Function "recording curve" (0E2) This function determines whether the envelope curve is read as • single curve or • cyclic ⇒ ENDRESS + HAUSER – Note! If the envelope curve mode is active on the display, the measured values are updated in a slower cycle time.
  • Page 42 Commissioning Levelflex M FMP45 PROFIBUS PA Endress+Hauser...
  • Page 43 Levelflex M FMP45 PROFIBUS PA Commissioning Endress+Hauser...
  • Page 44 www.endress.com/worldwide KA01045F/00/EN/13.10 71120328 CCS/FM+SGML 6.0 71120328...