OUTDOOR UNIT/3-PHASE MODEL
This equipment complies with EN/IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equals to 1850 kVA at
the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment
to ensure; by consultation with the distribution network operator if necessary that the equipment is connected only to supply with a
short-circuit power Ssc greater than or equals to 1850 kVA.
Ssc : Short circuit power
SG : Shows the ground for the shielded cable.
Model name
U-200PE2E8A
U-250PE2E8A
*
1 Use a shielded cable for the control cable. Overall extension less than 1000m.
Decide the length and size of the power supply cable based on the maximum ampere tabulated above in accordance with the
national wiring regulations.
Select the fuse(s) and/or circuit breaker(s) from the types and ratings suitable for the maximum ampere tabulated above in
accordance with the national wiring regulations.
If capacity of power supply circuit and enforcement are not enough, it can causes the electric shock and a fi re.
For the shield part of the shielded cable, twist the end out, crimp it with a
round terminal, and connect it to the SG screw.
After crimping it with a round terminal, wrap it with insulating tape so there
are no spaces and adjust it so the shield part does not touch any live parts.
Be sure that the shield part of the shielded cable does
CAUTION
not touch the terminal block or any live parts.
Failure to do so may lead to electric shock or fi re.
Power supply (220/230/240V~)
C
c r i
i u
b t
e r
k a
r e
Switch
Earth
L
N
Control cable
SG
U1
U2
R1
R2
2
1
Wired remote
Indoor unit
controller
Maximum electric
Power supply
current
380/400/415V 3N~
20 A
380/400/415V 3N~
20 A
Power supply (380/400/415V 3N~)
C
c r i
i u
b t
e r
k a
r e
Switch
L1
L2
L3
N
Earth
SG
U1
U2
Outdoor unit
*
1
Control cable
0.75 mm ²
1850 kVA
0.75 mm ²
1850 kVA
Crimp the round terminal
Shield part
1-24
Ssc
Wrap it well with insulating
tape so there are no spaces.