2.8.2 Installing Input Fuses
Installing fuses on the drive input side is recommended to prevent internal short circuit. Select
the suitable fuses below or the branch circuit protection in compliance with local electrician
regulations.
Three Phase
400V Model
0.4kW (0.5 HP)
0.75kW (1 HP)
1.5kW (2 HP)
2.2kW (3 HP)
3.7kW (5 HP)
ingle phase
200V Model S
0.2kW (0.25 HP)
0.4kW (0.5 HP)
0.75kW (1 HP)
1.5kW (2 HP)
2.2kW (3 HP)
Three Phase
200V Model
0.2kW (0.25 HP)
0.4kW (0.5 HP)
0.75kW (1 HP)
1.5kW (2 HP)
2.2kW (3 HP)
3.7kW (5 HP)
Input Current I (A)
2.7
4.4
6.7
9.3
12.9
Input Current I (A)
3.6
7.4
13.5
24
33
Input Current I (A)
2.2
3.7
6.6
10.5
14.8
21.5
14
Line Fuse
I (A)
5
10
10
15
20
Line Fuse
I (A)
6
10
20
30
40
Line Fuse
I (A)
5
5
10
15
20
30
Bussmann P/N
FRS-R-5
FRS-R-10
FRS-R-10
FRS-R-15
FRS-R-20
Bussmann P/N
FRS-R-6
FRS-R-10
FRS-R-20
FRS-R-30
FRS-R-40
Bussmann P/N
FRS-R-5
FRS-R-5
FRS-R-10
FRS-R-15
FRS-R-20
FRS-R-30