6.3 Operation Errors

Keypad
Error Name
Display
Parameter Range
oE02
Setting Error
Multi-Function
oE03
Input Selection
Error
3-Wire
oE04
Control
Error
Communication
oE05
Error
PID Control
Selection Fault
oE09
(When b5-00 (PID
Control Setting)= 1
to 4)
V/F Data Setting
oE10
Error
Table 6.3 Error Displays, Causes, and Possible Solutions
Parameters are set outside of
the possible setting range
1. Either of Up command and
Down command is not set
(
10 or 11 )
E1-□□=
2. Either of Up command 2
and Down command 2 is not
set (
E1-□□=
Multi-Function input
Sequence
terminals S1 and S2 are
Setting
assigned to
Sequence)
1. Contradictory settings
· b5-14 (PID Sleep Start
Level) is not set to 0.0
· b1-02 (Stopping Method
Selection) is set to 2 (DC
Braking to Stop) or 3 (Coast
to Stop with Timer)
2. L2-01 (Frequency
Command Lower Limit)≠0
when b5-00 = 1 or 2 (PID
Control Enabled)
3. b5-10 (PID Output Reverse
Selection) = 1 (Reverse
Enabled) when b5-00 = 1 or
2
4. L2-01 ≠ 0 when b5-00 = 3
or 4
V/F parameters setting
incorrect
Cause
12 or 13)
2 (3-Wire
E1-□□=
90
Possible Solution
1. Set the parameters to the
proper values
2. Reset the drive
Properly assign both of the UP and
Down commands to the multi-
function input terminal.
Do not assign multi-function input
terminals S1 and S2 to E1-□□= 2 (3 –
uence)
Wire Seq
1. Correct the parameter setting.
2. Correct the parameter setting.
3. Correct the parameter setting.
4. Correct the parameter setting.
Correct the setting in d1-02, d1-04,
d1-06, d1-08 and d1-09.