Main Circuit Terminal; Main Circuit Wiring - LiteOn EVO6000 Series Quick Start Manual

Ultra compact vector drive
Hide thumbs Also See for EVO6000 Series:
Table of Contents

Advertisement

4.2.1 Main Circuit Terminal

MCCB MC
R
S
T
Fast Acting Fuse
Terminal Name
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
+, -
E

4.2.2 Main Circuit Wiring

4.2.2.1 Power Input Terminal
Install a molded case circuit breaker (MCCB) between three phase AC input power and
main circuit terminals R/L1, S/L2 and T/L3. A magnetic contactor (MC) in series
connection is also suggested so as to shut off the power by drive protection functions.
Install a R-C varistor on both ends of the MC.
Ensure main circuit terminal screws are tightened to avoid vibration loosening the screws
which could cause electric sparks.
4.2.2.2 Power Output Terminal
When connecting a noise filter at AC drive output terminals U/T1, V/T2 and W/T3, always
use an inductive L-filter. Do not install any power capacitor, L-C or R-C filter.
Connect AC drive output terminals U/T1, V/T2 and W/T3 to motor input terminals U, V
R/L 1
S/L 2
T/L 3
Table 4.2.1 Main Circuit Terminals
Power input terminal
Power output terminal
Braking unit terminal. Select option as per the specifications.
Ground terminal
Braking Unit (option)
+
-
Terminal Description
21
U/T 1
V/T 2
W/T 3
E
IM

Hide quick links: