Keypad
Error Name
Display
Incorrect d1-02, d1-
04, d1-06, d1-08,
d1-09 settings
Carrier Frequency
oE11
Setting Error
Improper setting of
oE17
motor rated speed

6.4 Auto-Tuning Fault Detection

Table 6.4 Auto-Tuning Codes, Causes, and Possible Solution
Keypad
Fault Name
Display
TF00 Auto-Tuning Stop
Line-to Line
TF01
Resistance Error
Cause
1. Contradictory settings
· C6-03 (Carrier Frequency
Proportional Gain)>6
· C6-02 (Minimum Carrier
Frequency)> C6-01
(Maximum Carrier
Frequency)
Note: If C6-03 ≤ 6 , the drive
operates at C6-01
2. The upper and lower limit
set in C6-00 to C6-03 are
contradictory.
1. The following is also set.
· C6-03 (carrier frequency
proportional gain) >6
· C6-02 > C6-01
(lower carrier frequency >
upper carrier frequency)
(Note) When C6-03 ≤ 6, press
the fixed value of C6-01
2. The upper and lower limits
of C6-00~-03 are set
incorrectly.
Cause
User presses STOP key
during Auto-Tuning
The line-to-line resistance in
Auto-Tuning is negative or
limited by the upper the
lower limit
91
Possible Solution
Correct the parameter setting.
Correct the parameter setting.
Possible Solution
Do not press STOP key during Auto-
Tuning
Check and correct motor wiring

Hide quick links: