Carrier ComfortVu TB-24-HM Installation And Operation Manual page 61

Bacnet thermostat standard (24 vac model)
Hide thumbs Also See for ComfortVu TB-24-HM:
Table of Contents

Advertisement

Technician Settings (cont.)
P189 – Dehumidification cycle in unoccupied mode
Range:
0...600 minutes
Default:
20 minutes
P190 – Dehumidification break time in unoccupied mode
Range:
0...900 minutes
Default:
40 minutes
P192 – Temperature setpoint for re-heat in unoccupied mode
Range:
10...30ºC / 50...86ºF
Default:
15ºC / 59ºF
P193 – Display switching time (between temperature and humidity)
Range:
0...11 seconds
Default:
5 seconds
P194 – Humidity differential band
Range:
0...10 %RH
Default:
5%RH
P195 – Humidity sensor reading offset
Range:
-9...+9 %RH
Default:
0 %RH
- 61 -
Dehumidification
cycle in unocc. mode
Dehumidification
break in unocc. mode
Setpoint for reheat
in unocc. mode
Display switching
time Hum./Temp.
Humidity differential
band
Humidity
offset

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Comfortvu tb-24

Table of Contents