Carrier ComfortVu TB-24-HM Installation And Operation Manual page 57

Bacnet thermostat standard (24 vac model)
Hide thumbs Also See for ComfortVu TB-24-HM:
Table of Contents

Advertisement

Technician Settings (cont.)
P89 – De-ice in heat – cut-in temperature (AC only!)
Range:
-9.5...+8°C / 15...46°F
Default:
0°C / 32°F
The outdoor unit coil temperature in which de-icing will start.
P90 – De-ice in heat – cut-out temperature (AC only!)
Range:
2...20°C / 35...68°F
Default:
16°C / 61°F
The outdoor unit coil temperature in which de-icing will stop.
P91 – Compressor delay (AC only!)
Range:
0...360 Seconds
Default:
240 Seconds
DIP Switch SW3.5 must be in "OFF" position – compressor delay enabled!
P98 – Display setpoint only (hide room temperature)
"00" - Display both setpoint and room temperatures
"01" - Display only the setpoint temperature
P99 – One or Two setpoints (for cool and for heat)
"00" - One setpoint for cooling and heating
"01" - two setpoints – one for cool and one for heat
- 57 -
De-ice in heat
(°C)
(°F)
De-ice in heat
(°C)
(°F)
Compressor
delay
Show room
Hide room
temperature
temperature
One
Two
setpoint
setpoints