Technician Settings - Carrier ComfortVu TB-24-HM Installation And Operation Manual

Bacnet thermostat standard (24 vac model)
Hide thumbs Also See for ComfortVu TB-24-HM:
Table of Contents

Advertisement

Technician Settings (cont.)
P43 – P44
Soft start in heat
with fan on demand
(auto fan) active.
Heat valve
Fan
P43 – Soft start in heat – cut-in temperature (FC Only!)
The fan will not start before the temperature
on T3 sensor reaches the cut-in temperature.
See Technician Settings P08/P09.
Range:
14...37°C / 57...99°F
Default:
36°C / 97°F
P44 – Soft start in heat – cut-out temperature (FC Only!)
The fan will stop if the temperature on T3 sensor
drops below the cut-out temperature.
See Technician Settings P08/P09.
Range:
12...35°C / 54...95°F
Default:
32°C / 90°F
ON
OFF
Fan cut-out
temperature
- 47 -
T3
Temp.
Fan cut-in
temperature
Soft start heat cut-in temperature
(°C)
(°F)
Soft start heat cut-out temperature
(°C)
(°F)