Provide Clearances - Bryant 582A Installation, Start-Up, And Operating Instructions Manual

Single packaged gas heating/ electric cooling units
Table of Contents

Advertisement

HVAC unit
Screw
(NOTE A)
*Gasketing
outer flange
Flashing field
supplied
Roofing material
field supplied
Cant strip
field supplied
*Provided with roofcurb
Roof Curb for Small Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
44
(1125.5mm)
Return opening
(B X C)
UNIT SIZE
582A018-042
583A024-036
582A048-060
583A042-060
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimensions in ( ) are in millimeters.
4. Roof curb is made of 16-gage steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1-in. thick fiberglass 1 lb density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic
conditions. This bracket is available through Micrometl.
openings. Installation of flexible duct connector is recommended
to prevent transmission of vibration and /or noise to structure. All
ductwork should be secured to the flanges. Insulate and weather-
proof all external ductwork, joints, and roof openings with counter
flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire codes.
base
Gasketing
inner flange*
Wood nailer*
Roofcurb*
Insulation (field
supplied)
Duct work
field supplied
Roof
Supply opening
(B x C)
B Typ.
D
C Typ.
5
"
/
16
Insulated
deck pan
Long
Support
ODS CATALOG NUMBER
CPRFCURB006A00
CPRFCURB007A00
CPRFCURB008A00
CPRFCURB009A00
Fig. 4—Roof Curb Dimensions
R/A
A
Insulated
Short
Support
deck pan
A
IN. (MM)
8 (203)
14 (356)
8 (203)
14 (356)
A minimum clearance is not required around ductwork. Cabinet
return-air static shall not exceed -.25 in. wg.
IV. PROVIDE CLEARANCES
The required minimum operating and service clearances are shown
in Fig. 2 and 3. Adequate combustion, ventilation and condenser
air must be provided in accordance with section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code ANSI
(American National Standards Institute) Z223.1 or applicable
—5—
HVAC unit
base
Gasketing
inner flange*
Screw
(NOTE A)
*Gasketing
outer flange
Wood nailer*
Flashing field
supplied
Insulation (field
Roofing material
field supplied
Duct work
Cant strip
field supplied
field supplied
Roof
*Provided with roofcurb
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
Gasket around
duct
Gasket around
outer edge
B
C
IN. (MM)
IN. (MM)
11(279)
161/2 (419)
11(279)
161/2 (419)
16 3/16 (411)
17 3/8 (441)
16 3/16 (411)
17 3/8 (441)
Roofcurb*
supplied)
S/A
C00076
D
IN. (MM)
28-3/4 (730)
28-3/4 (730)
40-1/4 (1022)
40-1/4 (1022)

Hide quick links: