Auxiliary Limit Switch (Rollout); Start-Up Cooling And Make Adjustments; Checking Cooling Control Operation; Checking And Adjusting Refrigerant Charge - Bryant 582A Installation, Start-Up, And Operating Instructions Manual

Single packaged gas heating/ electric cooling units
Table of Contents

Advertisement

TABLE 7—AIR DELIVERY (CFM) AT INDICATED TEMPERATURE RISE AND RATED HEATING INPUT
HEATING
INPUT
20
(BTUH)
40,000
1500
60,000
2250
90,000
115,000
130,000
NOTE: Dashed areas do not fall within the approved temperature rise range of the unit.
TABLE 8—LED INDICATIONS
ERROR CODE
Normal Operation
Hardware Failure
Fan On/Off Delay Modified
Limit Switch Fault
Flame Sense Fault
Four Consecutive Limit Switch Faults
Ignition Lockout Fault
Induced-Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
Temporary lock-out (1 hr)
NOTES:
1. There is a 3-sec. pause between error code displays.
2. If more than one error code exists, all applicable error codes will be
displayed in numerical sequence
3. This chart is on the wiring diagram located inside the burner access panel.
When the air temperature at the limit switch drops to the
low-temperature setting of the limit switch, the switch closes and
completes the R control circuit. The electric-spark ignition system
cycles and the unit returns to normal heating operation.
H. AUXILIARY LIMIT SWITCH (ROLLOUT)
The function of the switch is to close the main gas valve in the
event of flame rollout. The switch is located above the main
burners. When the temperature at the auxiliary switch reaches the
maximum allowable temperature, the R control circuit trips,
closing the gas valve and stopping gas flow to the burners. The
indoor (evaporator) fan motor (IFM) and induced draft motor
continue to run until switch is reset. The IGC LED will display
FAULT CODE 7.
III. START-UP COOLING AND MAKE ADJUSTMENTS
CAUTION: Complete the required procedures given in
the Pre-Start-Up section before starting the unit.
Do not jumper any safety devices when operating the
unit.
Do not operate the compressor when the outdoor tem-
perature is below 40°F (unless accessory low-ambient kit
is installed).
Do not rapid-cycle the compressor. Allow 5 minutes
between ''on'' cycles to prevent compressor damage.
A. CHECKING COOLING CONTROL OPERATION
Start and check the unit for proper cooling control operation as
follows:
1. Place room thermostat SYSTEM switch in OFF position.
Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is
placed in AUTO. position.
25
30
35
1200
1000
857
1800
1500
1286
2250
1929
2464
2786
LED INDICATION
On
Off
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
TEMPERATURE RISE °F
40
45
50
750
667
600
1125
1000
900
1688
1500
1350
2156
1917
1725
2438
2167
1950
2. Place SYSTEM switch in COOL position and FAN switch
in AUTO. position. Set cooling control below room tem-
perature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle
shuts down when control setting is satisfied. The evaporator
fan will continue to run for 30 sec.
3. When using an auto-changeover room thermostat, place
both SYSTEM and FAN switches in AUTO. positions.
Observe that unit operates in Heating mode when tempera-
ture control is set to ''call for heating'' (above room
temperature) and operates in Cooling mode when tempera-
ture control is set to ''call for cooling'' (below room
temperature).
IMPORTANT: Three-phase, scroll compressor units
(582A048 and 583A030-060) are direction-oriented. These
units must be checked to ensure proper compressor 3-phase
power lead orientation. If not corrected within 5 minutes,
the internal protector shuts off the compressor. The 3-phase
power leads to the unit must be reversed to correct rotation.
When turning backwards, scroll compressors emit elevated
noise levels, and the difference between compressor suction
and discharge pressures may be dramatically lower than
normal.
B. CHECKING
CHARGE
The refrigerant system is fully charged with R-22 refrigerant,
tested, and factory-sealed.
NOTE: Adjustment of the refrigerant charge is not required
unless the unit is suspected of not having the proper R-22 charge.
A superheat charging chart is attached to the outside of the service
access panel. The chart includes the required suction line tempera-
ture at given suction line pressures and outdoor ambient tempera-
tures.
An accurate superheat, thermocouple- or thermistor-type ther-
mometer, a sling psychrometer, and a gauge manifold are required
when using the superheat charging method for evaluating the unit
charge. Do not use mercury or small dial-type thermometers
because they are not adequate for this type of measurement.
CAUTION: When evaluating the refrigerant charge, an
indicated adjustment to the specified factory charge must
always be very minimal. If a substantial adjustment is
indicated, an abnormal condition exists somewhere in the
cooling system, such as insufficient airflow across either
coil or both coils.
Proceed as follows:
1. Remove caps from low- and high-pressure service fittings.
2. Using hoses with valve core depressors, attach low- and
high-pressure gauge hoses to low- and high-pressure service
fittings, respectively.
—20—
55
60
65
545
500
818
750
692
1227
1125
1038
1568
1438
1327
1773
1625
1500
AND
ADJUSTING
REFRIGERANT
70
964
1232

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

583a

Table of Contents