UNIT SIZE 583A
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Quantity (lb.)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows...Fins/in.
Face Area (sq ft)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor Hp (Rpm)
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Burner Orifice No. (Qty...Drill Size)
Propane Gas
RETURN-AIR FILTERS (in.)†
Throwaway
* Based on altitude of 0 to 2000 ft.
† Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
ft/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
NOMINAL
INTERNAL
IRON PIPE,
DIAMETER
SIZE
(IN.)
(IN.)
½
.622
¾
.824
1
1.049
1.380
1.610
* Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on a 0.60 specific gravity gas). Refer to Table C-4, National
Fire Protection Association NFPA 54.
† This length includes an ordinary number of fittings.
8. Check for gas leaks at the field-installed and factory-
installed gas lines after all piping connections have been
completed. Use soap-and-water solution (or method speci-
fied by local codes and/or regulations).
IX. INSTALL DUCT CONNECTIONS
The unit has duct flanges on the supply- and return-air openings on
the side and bottom of the unit. For downshot applications, the
ductwork connects to the roof curb (See Fig. 2 and 3 for
connections sizes and locations).
A. CONFIGURING UNITS FOR DOWNFLOW (VERTI-
CAL) DISCHARGE
WARNING: Before performing service or maintenance
operations on the system, turn off main power to unit.
Electrical shock could cause serious injury or death.
1. Open all electrical disconnects before starting any service
work.
TABLE 2—PHYSICAL DATA—UNIT 583A (CONTINUED)
048090
4
421
8.3
.034
2...17
12.3
3300
22
¼ (1100)
4...15
4.7
1600
11 X 10
3/4 (1075)
3/4 (1075)
3...38
3...46
24 X 30
TABLE 3—MAXIMUM GAS FLOW CAPACITY*
10
20
30
40
175
120
97
82
360
250
200
170
680
465
375
320
1400
950
770
600
2100
1460
1180
990
048115
048130
4
4
421
421
Scroll
1
8.3
8.3
Acutrol Device
.034
.034
2...17
2...17
12.3
12.3
3300
3300
22
22
¼ (1100)
¼ (1100)
4...15
4...15
4.7
4.7
1600
1600
11 X 10
11 X 10
3/4 (1075)
3...33
3...31
3...42
3...41
24 X 30
24 X 30
LENGTH OF PIPE, FT†
50
60
70
80
73
66
61
57
151
138
125
118
285
260
240
220
580
530
490
460
900
810
750
690
2. Remove return duct cover located on duct panel by breaking
connecting tabs with screwdriver and a hammer (See Fig.
10A & 10B).
3. To remove supply duct cover, break front and right side
connecting tabs with a screwdriver and a hammer. Push
louver down to break rear and left side tabs (See Fig. 10A
& 10B).
4. If unit ductwork is to be attached to vertical opening flanges
on the unit composite base (jackstand applications only), do
so at this time.
CAUTION: Collect ALL screws that were removed. Do
not leave screws on rooftop as permanent damage to the
roof may occur.
5. It is recommended that the unit base insulation around the
perimeter of the vertical return-air opening be secured to the
unit base with aluminum tape. Applicable local codes may
require aluminum tape to prevent exposed fiberglass.
—10—
060090
060115
5
5
468
468
8.1
8.1
.032
.032
2...17
2...17
16.4
16.4
3300
3300
22
22
¼ (1100)
¼ (1100)
4...15
4...15
4.7
4.7
1750
1750
11 X 10
11 X 10
1.0 (1075)
1.0 (1075)
3...38
3...33
3...46
3...42
24 X 30
24 X 30
90
100
125
150
53
50
44
40
110
103
93
84
205
195
175
160
430
400
360
325
650
620
550
500
060130
5
468
8.1
.032
2...17
16.4
3300
22
¼ (1100)
4...15
4.7
1750
11 X 10
1.0 (1075)
3...31
3...41
24 X 30
175
200
77
72
145
135
300
280
460
430