Instructing The System User; Scanning And Resetting The "Service" Display - Viessmann VITODENS 200-W Service Instructions Manual

Type wb2b, 45 and 60 kw wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Further details regarding the individual steps
Press the following keys:
1. L + d simultaneously for
approx. 2 s.
The subscriber check
has been initiated.
2. a/b
for the required subscri-
ber.
3. d
Check is enabled
"Check" flashes until its
completion.
The display and all key
illuminations for the
selected subscriber flash
for approx. 60 s.

Instructing the system user

The system installer must hand the operating instructions to the system user
and instruct him/her in the operation of the system.

Scanning and resetting the "Service" display

The red fault indicator flashes when the limits set via coding address "21" and
"23" have been reached. The programming unit display flashes:
On a constant temperature control unit:
The defaulted hours run or the defaulted interval with clock symbol "u" (sub-
ject to setting)
On a weather-compensated control unit:
"Service"
Note
Set code "24:1" and then code "24:0" if a service is carried out before the ser-
vice display is shown; the set service parameters for hours run and interval are
then reset to 0.
Press the following keys:
1. c
The service scan is active.
Commissioning, inspection, maintenance
(cont.)
4. "Check OK" is displayed during
communication between both
devices.
or
"Check not OK" is displayed if
there is no communication
between both devices. Check the
LON connection.
5. Repeat points 2 and 3 to check
further subscribers.
6. L + d simultaneously for
approx. 1 s.
The subscriber check is
completed.
2. a/b Scan service messages.
35