Gas Type Conversion (Only For Operation With Lpg); Function Sequence And Possible Faults - Viessmann VITODENS 200-W Service Instructions Manual

Type wb2b, 45 and 60 kw wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Further details regarding the individual steps
Wobbe index ranges
Gas type
Delivered condition
Natural gas E
or
Natural gas LL
After conversion
LPG P

Gas type conversion (only for operation with LPG)

Function sequence and possible faults

Control unit is-
sues heat de-
mand
Commissioning, inspection, maintenance
Wobbe index range
3
kWh/m
12.0 to 16.1
10.0 to 13.1
20.3 to 21.3
1. Set adjusting screw A at the gas
train to "2".
2. Switch ON/OFF switch "8" ON.
3. Adjust the gas type in coding
address "82" (for a detailed
description of the individual steps,
see page 88):
Call up code 2
In coding address "11", select
value "9"
In coding address "82", select
value "1" (operation with LPG)
In code "11" select value
Terminate code 2.
4. Open the gas shut-off valve.
Display screen
No
(cont.)
3
MJ/m
43.2 to 58.0
36.0 to 47.2
72.9 to 76.8
"9".
Measures
Increase set
value and ensure
heat is drawn off
11