Viessmann VITODENS 200-W Service Instructions Manual page 36

Type wb2b, 45 and 60 kw wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
3. d
The service display will be
cleared (for a weather-
compensated control unit:
"Acknowledge: Yes",
reconfirm with d).
The red fault display con-
tinues to flash.
After a service has been carried out
1. Reset code "24:1" to "24:0".
The red fault indicator extin-
guishes.
Note
If coding address "24" is not reset,
the "Service" message reappears:
On a constant temperature con-
trol unit:
After 24 hours
On a weather-compensated con-
trol unit:
At 07:00 h on Monday
36
(cont.)
Note
An acknowledged service message
can be redisplayed by pressing d
(approx. 3 s).
2. Reset the burner hours run, burner
starts and consumption, if required.
Press the following keys:
c
Scanning is active.
a/b
for the selected value.
e
The selected value will be
set to "0".
a/b
for further scans.
d
Scanning is completed.