Advertisement

5 Advanced Operations

5-19 Displaying PV/SV Status

5-19-1 PV and SV Status Display Functions

 PV Status Display Function (Advanced Function Setting Level)
The PV on the No. 1 display in the PV, PV/SP, PV/Manual MV, or PV/SP Manual MV Display and the
control or alarm status specified for the PV status display function are alternately displayed in 0.5-s
*1
cycles.
• PV
*2
• PV/SP
• PV/Manual MV (Valve Opening)
• PV/SP/Manual MV (Valve Opening)
*1 This includes the displays specified with the PV/SP No. 1 and PV/SP No. 2 Display Selection parameters.
*2 This includes when the PV/SP is selected for the Monitor/Setting Item parameter.
Set value
OFF
Manual
Stop
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 1 to 4 OR status alm
Heater Alarm
Status display mes-
sage*
Note: The default is OFF.
* Selection is possible only with the E5DC, E5DC-B and E5GC. (The E5DC must be manufactured in July
2014 or later (version 2.2 or higher).)
Example: When STOP Is Selected for the PV Status Display Function
 SV Status Display Function (Advanced Function Setting Level)
The SP, Manual MV, or blank on the No. 2 display in the PV/SP, PV, or PV/Manual MV Display and
the control or alarm status specified for the SV status display function are alternately displayed in
*1
0.5-s cycles.
• PV
*2
• PV/SP
• PV/Manual MV (Valve Opening)
• PV/SP/Manual MV (Valve Opening)
*1 This includes the displays specified with the PV/SP No. 1 and PV/SP No. 2 Display Selection parameters.
*2 This includes when the PV/SP is selected for the Monitor/Setting Item parameter.
5 - 58
Display
No PV status display
off
MANU is alternately displayed during manual control.
manu
STOP is alternately displayed while operation is stopped.
stop
ALM1 is alternately displayed during Alarm 1 status.
alm1
ALM2 is alternately displayed during Alarm 2 status.
alm2
ALM3 is alternately displayed during Alarm 3 status.
alm3
ALM4 is alternately displayed during Alarm 4 status.
alm4
ALM is alternately displayed when Alarm 1, 2, 3, or 4 is set to ON.
HA is alternately displayed when an HB alarm or HS alarm is ON.
ha
While one or more of the work bits (WR1 to WR8) is ON, the message
for the highest bit number that is ON is alternately displayed with the
wr
corresponding bit number.
Normal
25
PV/SP
100
Function
When RUN/STOP
is STOP
Alternating
display
stop
100
E5@C Digital Temperature Controllers User's Manual (H174)