9.7. Error processing

The following tables list the errors that occur during executing this program.
9.7.1.
CMND Instruction Error Code
H400 stores the end code of the network communications instruction.
[Format]
Bit
15
Main response code
[Response codes (Excerpt)]
Main
Sub
02
05
10
04
25
05
Additional Information
For details, refer to 5-1-3 End Codes in 5-1 Command Lists in SECTION 5 FINS Commands
of the CJ Series Communications Commands REFERENCE MANUAL (Cat. No. W342).
Additional Information
For details on the CMND instruction error and troubleshooting, refer to 12-3 Troubleshooting
in SECTION 12 Troubleshooting and Maintenance of the CJ Series Serial Communications
Units OPERATION MANUAL (Cat. No. W336).
9.7.2.
Transmission error status
H401 stores contents of the transmission error status ''1508''.
[Contents of each bit in the transmission error status]
Bit
15
1: Transmission error
8 to 14
(Not used)
7
1: FCS check error
6
(Not used)
5
1: Timeout error
4
1: Overrun error
3
1: Framing error
2
1: Parity error
0, 1
(Not used)
8
7
Sub-response code
Main response code
Destination node error
Command format error
Unit error
Description
0: No transmission error
0: FCS check normal
0: Normal
0: Normal
0: Normal
0: Normal
0
Sub-response code
Response timeout
Command format error
CPU Bus Error