Cable Wiring Diagram - Omron CJ Series Connection Manual

General-purpose serial, rs-485 modbus communication, multi-function compact inverter
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

6.2. Cable Wiring Diagram

Refer to SECTION 3 Installation and Wiring of the CJ Series Serial Communications Units
OPERATION MANUAL (Cat. No. W336) for details on cable wirings.
Check connector configurations and signal lines (pin assignments) before wiring.
■Connector configurations and signal lines (pin assignments)
CJ1W-SCU42 Serial Communications Unit applicable connector: Terminal block
Pin No.
1(See note 1.)
2(See Note 1.)
3(See Note 1.)
4(See Note 1.)
5(See Note 2.)
Note 1: For 2-wire connection, use either pins 1 and 2 or pins 3 and 4.
Note 2: Pin 5 (Shield) is connected to the GR terminal on Power Supply Unit though Serial
Communications Unit. The cable shield can thus be grounded by grounding the GR
terminal of Power Supply Unit.
Inverter (3G3MX2-A[][][][]-V1) applicable connector: Terminal block
Control Circuit Terminal
■Cable/Pin assignments
Serial Communications Unit
(CJ1W-SCU42).
RS-422A/
Signal
485
name
interface
RDA-
RDB+
SDA-
SDB+
FG
Terminal block
Symbol Signal name
RDA
Receive data -
RDB
Receive data +
SDA
Send data -
SDB
Send data +
FG
Shield
Pin No.
1
Terminating resistor
2
3
4
5
6.Serial Communications Settings
Input/Output
Input
Input
Output
Output
-
Inverter (3G3MX2-A[][][][]-V1)
Terminal
Signal
block
name
A1
RS-
B1
RS+
Terminal block
RS-485
interface
9

Advertisement

Table of Contents
loading