To commission the pressure transmitter for liquids, proceed as follows:
1. Open both the shut-off valves
2. Open the stabilizing valve
3. With pressure transmitters below the differential pressure transducer, partially open both
drain valves
In the case of a pressure transmitter above the differential pressure transducer, partially
open both vent valves
4. Close both drain valves
5. Partially open the differential pressure valve
valve) on the positive side of the pressure transmitter until liquid escapes without bubbles.
6. Close the vent valve (sealing plug with vent valve).
7. Partially open the vent valve (sealing plug with vent valve) on the negative side of the
pressure transmitter until liquid escapes without bubbles.
8. Close the differential pressure valve
9. Partially open the differential pressure valve
10.Close the differential pressure valve.
11.Close the vent valve (sealing plug with vent valve) on the negative side of the pressure
transmitter.
12.Open the differential pressure valve
13.For a lower range value of 0 bar, check the zero point (4 mA) and correct the lower range
value if it is different.
14.Close the stabilizing valve
15.Open the differential pressure valves (
6.5.3
Commissioning with vapor
Requirement
All valves are closed.
Hot vapor
Danger of injury or damage to device.
If the shut-off valves
valve
● Follow the specified procedure for commissioning.
SITRANS P320/P420 with 4 to 20 mA/HART
Compact Operating Instructions, 09/2018, A5E38874562-AB
⑦
one after the other until liquid emerges without bubbles.
⑩
⑦
WARNING
⑥
and the differential pressure valve
②
is then opened, the pressure transmitter
⑥
at the pressure tapping point.
②
.
one after the other until liquid emerges without bubbles.
⑩
or vent valves
.
③
and the vent valve (sealing plug with vent
③
.
④
until liquid escapes without bubbles.
③
with half a revolution.
②
.
③
④
and
) completely.
①
6.5 Differential pressure and flow rate
③
are both open and the stabilizing
can be damaged by the flow of vapor.
Commissioning
51