3. Connection and Wiring
• Remove the cover of the window for pulling out the extension block connector cable provided on
the right side of the LE-40MTB-E. Insert the LE-60EC type extension cable for the extension block sold
separately into the connector provided inside the connector cable pull-out window. Connect the FX2N-
32CCL type interface block to the connector with the lock lever provided on the opposite side.
• Refer page 7 to 9 of FX2N-32CCL type interface block User's manual for the details of the power cable
and the connection cable to the CC-Link.
4. Setting the Station Numbers
• The local station numbers are required to be set to assign the address of the local stations to the master
unit in the network. When the station numbers are set, the buffer memory is assigned for each local
station on the master unit side. Set the station numbers of #1 to #64 using the station number setting
switches on the FX2N-32CCL.
• Next, set the occupied station number using the occupied station number setting switches on the FX2N-
32CCL. This number can be set to one to four for the FX2N-32CCL. However, the number of data de-
vices to be linked to the LE-40MTB-E is limited to ten because of the specifications of the relation with
other programmable controller link. Four devices per station can be linked in the FX2N-32CCL, there-
fore, set the occupied station number to three when connecting with the LE-40MTB-E. Note that ten
data devices can be linked to the LE-40MTB-E at the maximum. Even if the occupied station number
are set to four, the number of data devices to be linked remains ten.
• For example, when "#15" is set, three stations "#15, #16 and #17 are occupied. Never use a number
which is already set for an other station.
Make sure to turn off the LE-40MTB-E when setting the station number and the occupied station num-
ber. If the setting is carry out with the LE-40MTB-E on, "L ERR" on the FX2N-32CCL blinks and the
system considers it as an error.
Cover of connector cable pullout window
LE-40MTB-E
55
FX2N-CNV-BC
LE-60EC
FX2N-32CCL