10. Appendix 2 Setting Procedure without the Configuration Files
10.3.3. Setting Global Variables
Set global variables used for the remote I/O communications.
1
Double-click Global variables
under Programming - Data in
the Multiview Explorer.
2
The Global Variables Tab is
displayed in the Multiview
Explorer.
Click a Name Cell to enter a new
variable.
Enter DN00_CMD_OUT in the
Name Column.
Enter BOOL[16] in the Data
Type Column.
*When the data have been
entered, ARRAY[0..15] OF
BOOL is displayed as shown on
the right figure.
Enter %3200 in the AT Column.
3
After entering values, right-click
and select Create New from the
menu.
4
Enter the following data in the
new cells in the same way as
step 2.
•Name: DN00_DATA_OUT
Data Type: WORD
AT: %3201
5
Enter the following data in the
new cells in the same way as
steps 2 and 3.
•Name: DN00_STA_IN
Data type: B
OOL[16]
AT: %3300
Name: DN00_DATA
Data Type: WORD
AT: %3301
_IN
46