Siemens CC-2M Directions For Use Manual page 56

Table of Contents

Advertisement

Available languages

Available languages

English
– Seismic Vibration
IEC 60255-21-3, Class 1
IEC 60068-3-3
Vibration and Shock Stress During Transport
Standards:
– Vibration
IEC 60255-21-1, Class 2
IEC 60068-2-6
– Shock
IEC 60255-21-2, Class1
IEC 60068-2-27
– Continuous Shock
IEC 60255-21-2, Class 1
IEC 60068-2-29
Climatic Stress Tests
Temperatures
– Recommended temperature during operation –5 °C to +55 °C
– Permissible temporary (transient)
operating temperature
– Type test (acc. IEC 60068–2–1 and –2
Test Bd for 16 h)
– Limit temperatures during storage
– Limit temperatures for operation
Storage and transport of the device with factory packaging!
56
Sinusoidal
1 Hz to 8 Hz ± 3.5 mm Amplitude
(horizontal axis)
1 Hz to 8 Hz: ± 1.5 mm Amplitude
(Vertical axis)
8 Hz to 35 Hz: 1 g acceleration
(horizontal axis)
8 Hz to 35 Hz: 0.5 g acceleration
(Vertical axis)
Frequency Sweep Rate 1 Octave/min
1 cycle in 3 orthogonal axes
IEC 60255-21 and IEC 60068-2
Sinusoidal
5 Hz to 8 Hz: ± 7.5 mm Amplitude
8 Hz to 150 Hz: 2 g acceleration
Frequency sweep rate 1 Octave/min
20 cycles in 3 orthogonal axes.
Half-sine shaped
Acceleration 15 g, duration 11 ms,
3 shocks in each direction of
3 orthogonal axes.
Half-sine shaped
Acceleration 10 g, duration 16 ms,
1000 shocks in each direction of
3 orthogonal axes.
IEC 60068–2
–20 °C to +70 °C
–25 °C to +85 °C
–25 °C to +55 °C
–25 °C to +70 °C
7XV5662-0AD00