Electrical Tests - Siemens SIPROTEC 7SS522 V4.6 Manual

Distributed busbar/breaker failure protection
Hide thumbs Also See for SIPROTEC 7SS522 V4.6:
Table of Contents

Advertisement

ST_NOT
ST_OR
SUB
TIMER
TIMER_SHORT
UINT_TO_REAL
UPPER_SETPOINT
X_OR
ZERO_POINT
To find out which priority classes are associated with which function blocks, please
consult the DIGSI CFC Manual/3/.

9.2.14 Electrical Tests

CE conformity
This product complies with the directive of the Council of the European Communities
regulations
on the approximation of the laws of the member states relating to electromagnetic
compatibility (EMC Council Directive 89/336/EEC) and concerning electrical
equipment for use within specified voltage limits (Low Voltage Directive 73/23 EEC).
This conformity has been proved by tests performed according to Article 10 of the
Council Directive in agreement with the generic standards EN 61000-6-2 and EN
61000-6-4 (for EMC directive) and with the standard EN 60255-6 (for Low Voltage
Directive) by Siemens AG.
The device is designed and manufactured for application in industrial environment.
The product conforms with the international standards of IEC 60255 and the German
standard VDE 0435.
Insulation tests
Standards:
– High voltage test (routine test)
– High voltage test (routine test)
– High-voltage test
– Impulse voltage test (type test)
7SS52 V4 Manual
C53000-G1176-C182-3
Negator with status
OR gate with status
Subtraction
Universal timer
Simple timer
U-Int to Real, Adapter
Value above upper limit
(XOR gate)
Zero point suppression
all circuits except
auxiliary voltage input,
binary inputs, data interfaces
(service, system and clock
synchronization interface)
only auxiliary voltage input and
binary inputs
(routine test) only data inter-
faces (service,system and
clock synchronization interface)
all circuits without communication
and clock synchronization interface,
Class III
General Device Data
IEC 60255-5 and IEC 60870-2-1
2 kV AC (r.m.s. value); 50 Hz; 1 min
2.8 kV DC; 30 sec; both polarities
500 V AC (r.m.s. value); 50 Hz; 1 min
5 kV (peak value); 1.2 / 50 µs; 0.5 J;
3 positive and 3 negative pulses in
intervals of 5 s