Table of Contents

Advertisement

6.7

Electrical Tests

Standards
IEC 60255 (product standard)
IEEE Std C37.90
UL 508
Additional standards are listed for the individual tests.
Installation Requirements
Overvoltage category
Degree of pollution
Protection class
Voltage-Immunity and Safety Tests
Standards
Voltage test (routine test), current measurement inputs, voltage meas-
urement inputs, relay outputs
Voltage test (routine test),
Auxiliary voltage, binary inputs
Voltage test (routine test), only isolated communication and time-
synchronization interfaces and analog inputs (module position E, F, M,
N, and P)
Surge immunity test (type testing), all circuits except communication
and time-synchronization interfaces and analog inputs, class III
Insulation resistance
Resistor of protective-equipotential-bonding
Insulation of LPIT Digital Input (via Module IO240)
Insulation (All Inputs)
Configuration
Test levels (type test)
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-J, Edition 08.2020
Each phase group (current, voltage, and temperature) is insulated from
each other, to PE and to the operator according to the requirements of the
IEC 61869-1 (AC 3 kV, 50 Hz, 1 min) and the IEC 60255-27 for a rated
voltage of 300 V despite the low-level signal voltages.
All channels are protected with differential-mode and common-mode
voltage-limiting devices.
AC 3250 V, 50 Hz, 1 min
6000 V 1.2/50 µs peak impulse
Technical Data
6.7 Electrical Tests
III
2
1
IEC 60255-27
AC 2.5 kV
50 Hz
DC 3.5 kV
DC 700 V
5 kV (peak value)
1.2 µs/50 µs
0.5 J
3 positive and 3 negative impulses
at intervals of 1 s
> 100 MΩ @ DC 500 V
< 0.1 Ω @ DC 12 V, 30 A after
1 min.
235

Advertisement

Table of Contents
loading

Table of Contents