Port F
Ethernet optical (EN 100 O
multimode) for IEC 61850,
DIGSI
GPS Connection
Connection
PPS/IRIG-B
Connection
4.1.5

Electrical Tests

Regulations
Standards:
see also individual tests
Merging unit
IEC 60255
EN 60255/EN 50263
DIN 57435/DIN EN 50263
IEC TS 61000-6-5
IEC/EN 61000-4
IEC 60694
IEC 61850-3
ANSI/IEEE Std C37.90
IEC 61010-1
VDE 0435
SIPROTEC, 7SC805, Manual
C53000-G1140-C380-1, Release date 05.2014
+
Connection
Transmission speed
Fiber type
Permissible bending radii:
Maximum distance of transmission max.2 km for multimode
Transmitter
Optical wavelength c
Output power P
OUT
Receiver
Sensitivity P
Min
IN
Overload P
Max
IN
SMB socket (subminiature B) at device
Active GPS antenna
5 V, max. 50 mA
ST
multimode optical fiber G50 m/125 m, G62.5m/125 m
Bay units
IEC 60870
EN 60870
DIN EN 60870
IEC TS 61000-6-5
IEC/EN 61000-4
IEC 60694
IEC 61850-3
4.1 General Device Data
Duplex-LC, 100Base-FX in acc. with
IEEE802.3
100 Mbit/s
multimode optical fiber G50 m/125 m,
G62.5m/125 m
for indoor cable r
= 5 cm
min
for outdoor cable r
= 20 cm
min
1270 nm to 1360 nm
-15 dBm to -8 dBm
min. -31 dBm
max. -8 dBm
Technical Data