Safety Information - Siemens SINAMICS Series Equipment Manual

Booksize power modules
Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

2.3.2

Safety information

Caution
Line filters are only suitable for direct connection to TN systems.
Danger
The 100 mm clearances above and below the components must be observed. The mounting
position must ensure that cool air flows vertically through the filter. This measure prevents
thermal overloading of the filter.
Caution
The terminals must be correctly connected:
Incoming line cable to LINE/NETZ L1, L2, L3
Outgoing cable to line reactor on LOAD/LAST L1´, L2´, L3´.
Non-observance may damage the line filter.
Caution
The line filters listed conduct a high leakage current via the PE conductor. Because of the
high leakage current of the line filters, a permanent PE connection of the line filter or
switching cabinet is required.
Measures according to EN 61800-5-1 must be taken (e.g. PE conductor (≥10mm
an additional connection terminal for a PE conductor with the same cross-section as the
original PE conductor).
Warning
A hazardous voltage will be present at the terminals for a further 5 minutes after the system
has been shutdown.
Note
If a high-potential test is conducted with alternating voltage in the system, the line filters must
be disconnected to obtain correct measurement results.
Caution
Only the line filters described in this Equipment Manual must be used. Other line filters can
lead to line harmonics that can interfere with or damage other loads powered from the
network.
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
Line Connection Booksize