Overrides - Danfoss MCX-RTU User Manual

Rooftop unit
Table of Contents

Advertisement

User Guide | MCX-RTU Rooftop

Overrides

© Danfoss | ADAP-KOOL® | 2018.11
Overrides OV1 and OV2, are used to enable Night Setback and Title24 modes.
Overrides OV3 – OV8 are used to place the specific features (as shown below) in manual opera-
tion. The override value will be displayed by stage, %, OFF, ON, etc. For analog outputs a value of
zero shuts down the feature and 100 will enable 100% of the feature overridden.
OV0
Service > Over-
Function
rides
OV1
Override Night-
Override Night Setback – Enables Night
Setback
Setback(Off/On)
OV2
Override Title24
Override Title24 – Enables Title24(Off/On)
OV3
Override Fan
Override Fan(Auto/Override)
OV4
Override Fan %
Sets Speed of Fan when in Override(0.0 –
100.0)
OV5
Override Dam-
Override DamperAuto/
per
Off/25%/50%/75%/100%)
OV6
Override Cooling Override Cooling(Auto/Off/Stg1/Stg2/
Stg3/Stg4/All On)
OV7
Override Heat
Override Heat Reclaim(Auto/Off/Stg1/
Reclaim
Stg2/Stg3/Stg4/All On)
OV8
Override Aux
Override Aux Heat(Auto/Off/Stg1/Stg2/
Heat
Stg3/Stg4/All On)
OV9
Override Time-
Override Timeout – Removes override after
out
so much time (0-30)
Default
Units
Off
Off
Auto
0.0
%
Auto
Auto
Auto
Auto
0
m