3-10-3 Regenerative Energy Absorption by Regeneration
Resistor
If the Position Driver alone cannot absorb the regenerative energy, connect a Regeneration Resistor.
The Regeneration Resistor connects between the P and J terminals at the Position Driver's terminal
block.
Caution
Be careful when connecting the Regeneration Resistor. If done incorrectly it will
!
damage the Position Driver.
Caution
The Regeneration Resistor heats up to 120°C, so be careful not to place it near
!
equipment or wiring that may be affected by heat. Also be sure to install a radiation
shield that satisfies the heat radiation conditions.
H Selecting a Regeneration Resistor
D Types of Regeneration Resistors
Type
Model
A
R88A-RR20030
B
R88A-RR40030
D Regeneration Resistor Combinations
100 W
Combination
method
A
Note Select a combination with a capacity greater than the average regenerative power (P
D Dimensions (Unit: mm)
Model
R88A-RR20030
215
R88A-RR40030
265
3-78
Resistance
30Ω
200 W
30Ω
400 W
Regeneration absorption capacity
200 W
B
L1
200
250
Nominal
Regeneration
capacity
absorption at
120_C
100 W
200 W
400 W
A
A
A
A
L2
W
50
60
Chapter 3
Heat radiation
conditions
t3 × j350
(aluminum)
t3 × j350
(aluminum)
800 W
B
B
B
B
).
r
H
25
30