Pin assignment
The following table shows the signal name and description of the pin assignment of
BusAdapter BA 2×LC:
Table 9- 1
Requirements
● Prepare the IE FC FO cable with the IE FC FO LC plug connectors. For detailed
instructions, refer to the assembly instructions Preparing IE FC FO Cable with the plug-in
connector IE FC FO LC Plug (A5E36312721).
● When installing the fiber-optic cable, make sure the bending radius is not less than
permitted:
– IE FC FO Standard Cable GP (62.5/200/230): 70 mm
– IE FC FO Trailing Cable (62.5/200/230) (6XV1847-2C): 88 mm
● The maximum lengths of the fiber-optic cables are as follows:
– IE FC FO Standard Cable GP (62.5/200/230): 2 km
– IE FC FO Trailing Cable (62.5/200/230): 2 km
● When the interface module is the last device of the fiber-optic cable network, the
unoccupied fiber-optic cable interface must be closed with a blanking plug. When the
modules ship, the blanking plugs are inserted in the PROFINET sockets of the
BusAdapter.
BusAdapter
Manual, 03/2018, A5E41449003-AA
PROFINET IO pin assignment with BusAdapter BA 2xLC
View
Sig-
nal
name
Receive Data
Transmit Data
BusAdapter BA 2xLC
9.2 Connecting
Description
49