Siemens SIMATIC CP 440 Manual page 71

Installation and parameter assignment
Table of Contents

Advertisement

Protocol Parameters
The table below describes the protocol parameters.
Table 5-5
Protocol Parameters (ASCII Driver)
Parameter
End ID of a
Specifies the criterion that
Receive
indicates the end of each message
Message Frame
frame.
Character Delay
The character delay time defines
Time
the maximum permitted time
between 2 consecutively received
characters.
Monitoring Time
The character delay time is used
for Missing
as the monitoring time for a
End ID
missing end code. This applies to
the following settings for the end
code
– On Receipt of Fixed
– On Receipt of End
1
1st End ID
First end code.
1
2nd End ID
Second end code, if specified.
You can parameterize the following
for the end code:
– 1st end ID AND
– 1st end ID OR 2nd end ID
Message Frame
When the end criterion is "fixed
3
Length
message frame length", the
number of bytes making up a
message frame is defined.
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
Description
Number of Characters
Character
2nd end ID
Configuring and Parameterizing the CP 440
Value Range
On Expiry of Character
Delay Time
On Receipt of Fixed
Number of Characters
On Receipt of End
Character
1 to 65535 ms
The shortest character delay
time depends on the
transmission rate
bps
Character time
delay (ms)
300
130
600
65
1200
32
2400
16
4800
8
9600
4
19200
2
38400
1
57600
1
76800
1
115200
1
2
7 data bits
:
0 to 7FH (hex)
2
8 data bits
:
0 to FFH (hex)
2
7 data bits
:
0 to 7FH (hex)
2
8 data bits
:
0 to FFH (hex)
1 to 200 (bytes)
Default Value
On Expiry of
Character
Delay Time
4 ms
3 (03H =
ETX)
0
200
5-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents