Troubleshooting; Ciper Model 50 Controller Troubleshooting - Honeywell CIPer 50 Installation & Commissioning Instructions

Hide thumbs Also See for CIPer 50:
Table of Contents

Advertisement

CIPer MODEL 50 CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

TROUBLESHOOTING

CIPer Model 50 Controller Troubleshooting

The following LEDs of the CIPer Model 50 controller can be used for troubleshooting purposes:
Power LED (green)
Status LED (red)
L1 and L2 LEDs (yellow)
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LEDs
Power LED (green) of CIPer Model 50
case
power LED
meaning
1
ON
Normal operation.
Power supply not OK.
2
OFF
Status LED (red) of CIPer Model 50
case
status LED
meaning
!
Normal operation.
1
OFF after
power-up
2
ON con-
– Indicates an active alarm; is controlled
tinuously after
power-up
L1 LED
case
bus LED
meaning
L1
Normal operation; Daemon starting.
1
ON con-
tinuously after
power-up
Station starting; if L2 is also flashing, then
2
Flashes
the station has started.
constantly
Severe software problems.
3
OFF
31-00233EFS-01
Table 28. CIPer Model 50 controller power LED
Table 29. CIPer Model 50 controller status LED
by WEBs- Alarm System; is configurable.
Table 30. CIPer Model 50 controller bus L1 LED
remedy
No action necessary.
Check power supply voltage.
Check wiring.
If problem persists, replace hardware.
remedy
No action necessary.
Try powering down and then powering up the
CIPer Model 50 controller.
If problem persists, replace hardware.
remedy
No action necessary.
No action necessary.
Contact TAC.
44