Honeywell CIPer 50 Installation & Commissioning Instructions page 19

Hide thumbs Also See for CIPer 50:
Table of Contents

Advertisement

Powering Panel Bus I/O Modules and Field
Devices
The CIPer Model 50, Panel Bus I/O modules, and field
devices can be powered by either separate transformers
(see Fig. 25, and Fig. 26) or by the same transformer. Refer
to "Panel Bus I/O Modules Product Data Sheet" EN0B-
0701GE51 R0218.
NOTE: Use a min. distance of 10 cm between power
cables and 0...10 V / sensor cables in order to
prevent signal disturbances on the 0...10 V /
sensor cables. See also section "Addressing Panel
Bus I/O Modules" on page 301.
Powering Field Devices and Panel Bus I/O Module
via Separate Transformers
24 V actuator connected to, e.g., an analog output
module
Field device located 100 ... 400 m from the analog
output module
Fig. 25. Power supply via a separate transformer
Powering Field Devices via Panel Bus I/O Module
24 V actuator connected to, e.g., an analog output
module
Field device located max. 100 m from the analog output
module
Fig. 26. Power supply via Panel Bus I/O Module
CIPer MODEL 50 CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
19
31-00233EFS-01