Safety clearances between molded case circuit breakers
Minimum clearance to be maintained between two molded case circuit breakers installed
immediately above one another with different connection methods.
A
B
C
D
①
②
Figure 6-4
Table 6- 4
Molded case circuit
breaker type
Switching capacity
x ≤ 690 V
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
Font connection with cable, direct
Front connection with cable lug
Front connection with flat connecting bar
Rear connection with plug-in base or busbar terminals
Insulation
Insulation of busbar
Table of different connection types
Safety clearances to be maintained between molded case circuit breakers
VL160X
N, H
VL160
VL250
VL400
N, H, L
160 mm
Installing/mounting
6.2 Mounting and safety clearances
VL630
VL800
VL1250
N, H, L
200 mm
VL1600
83