Motorized operating mechanism (MO)
Table 11- 34 Motorized operating mechanism (MO)
Type of molded case circuit breaker
Type of motorized operating mechanism
(MO)
Power consumption
Rated control supply
voltage U
s
NEOZED fuse
(performance class
gL /gG)
Miniature circuit
breaker
(C characteristic in
accordance with
DIN VDE 0641)
1)
Operating range
Min. command duration
at U
s
Max. command
duration, connection-
dependent
1)
Total closing time
OFF time
Interval between the
commands OFF and
ON
Interval between the
commands ON and
OFF
Max. permissible
switching frequency
Switching capacity of
the floating contact
(switch position of the
mode selector)
Note the idle times between ON and OFF.
1)
3VL IEC molded case circuit breakers
System Manual, 11/2013, 110 0110 - 02 DS 03
3VL1
3VL9100-
3M_10
[VA / W]
50 / 60 Hz [V AC]
DC [V]
24 V
42 ... 60 V
110 V
220 V
24 V
42 ... 60 V
110 V
220 V
[V]
[ms]
[s]
[s]
[s]
[s]
[1 / h]
11.8 Motorized operating mechanisms
3VL2 / 3VL3
3VL4
3VL9300-
3VL9400-
3M_10
3M_10
< 100
42 ... 60 / 110 ... 127 / 220 ... 250
24 / 42 ... 60 / 110 ... 127 / 220 ... 250
6 A
6 A
4 A
2 A
C 6 A
C 6 A
C 4 A
C 2 A
0.85 ... 1.1 x U
Jog or continuous command
< 1
< 1
≥ 10
≥ 10
120
16 A / 250 V AC; 0.4 A / 125 V DC; 0.2 A / 250 V DC
(Switching capacity in accordance with UL 1054)
Technical data
3VL5 / 3VL6
3VL9600-
3M_10
s
50
3VL7 / 3VL8
3VL9800-
3M_10
< 150
30
157