Siemens SENTRON 3VL160X System Manual page 154

Iec molded case circuit breakers
Hide thumbs Also See for SENTRON 3VL160X:
Table of Contents

Advertisement

Technical data
11.7 Motor Protection
Molded case circuit breakers for motor protection with adjustable trip class ETU30M
Molded case circuit breaker characteristic
Table 11- 30 Molded case circuit breakers for motor protection with adjustable trip class ETU30M
Molded
case
circuit
breaker
VL160
VL250
VL400
VL630
154
curve for motor protection with
adjustable trip class ETU30M
Rated
Max. rated power of the
current I
motor at 50 Hz AC
n
[A]
[kW]
380 / 415 V
63
30
100
37, 45
160
55, 75
200
90, 110
250
132
315
160
315
200
500
250
These molded case circuit breakers possess
an adjustable overload and short-circuit
release and an adjustable trip class.
They are current-limiting and have a phase
failure sensitivity feature Communication via
PROFIBUS DP and Modbus RTU is possible.
Adjustable range
of the overload
protection I
R
[A]
500 V
37
0.41-1.0 x I
55
0.41-1.0 x I
75, 90
0.41-1.0 x I
110, 132
0.41-1.0 x I
160
0.41-1.0 x I
200
0.41-1.0 x I
250
0.41-1.0 x I
355
0.41-1.0 x I
System Manual, 11/2013, 110 0110 - 02 DS 03
Adjustable
Trip class TC
range of the
short-circuit
protection I
I
[A]
6/8/11 x I
n
n
6/8/11 x I
n
n
6/8/11 x I
n
n
6/8/11 x I
n
n
6/8/11 x I
n
n
6/8/11 x I
n
n
6/8/11 x I
n
n
6/8/12.5 x I
n
n
3VL IEC molded case circuit breakers
[s]
10/20/30
10/20/30
10/20/30
10/20/30
10/20/30
10/20/30
10/20/30
10/20/30